EXALT NATURAL GAS TO PROPANE CONVERSION INSTRUCTIONS
NOTICE
1.
Preliminary Instructions:
1.
Verify that the venturi replacement kit is correct for
the model of boiler. See page 1.
2.
Turn off electrical power supply to the boiler.
3.
Close the manual gas shut off valve to the unit.
4.
Remove the front panel of the Exalt.
For the floor standing model:
Remove the two securing screws on top of the
control pod. Rotate the pod upwards. Lift the front
panel to disengage the keyhole slots and remove
the panel.
Re-fit in the reverse order.
For the wall hung model
Remove the securing screw holding the bottom of
the front panel to the chassis. Pull the bottom of
the front panel out and lift to disengage from the
top mounting points.
Re-fit in the reverse order.
5.
Using a voltmeter ensure there is no electrical
power to the boiler by checking for power on the
boiler’s high voltage terminals L and N.
The Exalt boiler has a length of acoustic foam already
installed in the air inlet adaptor. DO NOT remove this
3.
Insert the length of acoustic foam (supplied),
into the 7" pipe length.
4.
Use either a straight coupling or elbow to
continue the air inlet installation. Refer to
the Vent Supplement for full details on the
installation of air and vent pipes.
ELECTRICAL SHOCK HAZARD
Ensure power to the boiler has been disconnected
prior to servicing the unit.
2.
Install the Acoustic Foam
The acoustic foam is only applicable to the 110 and 155
models. The Exalt 199 models do NOT use the additional
acoustic foam.
1.
Cut a 7" length of 3" diameter air inlet piping.
2.
Insert the 7" pipe into the air inlet adaptor.
Fig. 1: Installing the Acoustic Foam (applicable to 110
and 155 models ONLY)
NOTICE
!
WARNING
Acoustic
Foam
Acoustic
Foam
7" Air
Inlet
Pipe
7" Air Inlet
Pipe
Boiler
Air Inlet