EXALT NATURAL GAS TO PROPANE CONVERSION INSTRUCTIONS

 

 

NOTICE

 

WARNING

 

WARNING

 

NOTICE

 

 

 

5.

 

Combustion Test and Adjustments

 

 

The installer MUST perform a complete combustion check to 

ensure the following combustion levels are met at high and 

low input firing rates and the burner is operating at optimum 

conditions.

 

 

The combustion testing and adjustments must be 

performed by a qualified installer, service agency or 

the gas supplier. All combustion measurements must 

be performed with calibrated equipment to ensure 

proper readings and accuracy. Refer to Table 1 to 

check the combustion is within the acceptable range.

 

 

Failure to perform a complete combustion test at both 

high and low input rates may result in incomplete 

combustion and the production of carbon monoxide, 

which can cause severe personal injury, death or 

substantial property damage.

 

 

1.

 

Touch simultaneously on the up and down soft 

keys for 3 seconds to access the functions for the 

installer. See Fig. 5.

 

2.

 

Enter the installer access code “054” by using the 

LEFT and RIGHT buttons to select a digit and the UP 

and DOWN buttons to change the digit. Press the 

CENTER button to enter the access code.

 

3.

 

Press the RIGHT button to highlight the Manual 

Operation icon then press the CENTER button.

 

4.

 

Press the CENTER button while the FAN icon is 

highlighted to manually fire the burner and power 

the CH circulator. See Fig. 6.

 

 

 

An adequate CH load must be present to dissipate the heat 

generated during the combustion test. If an adequate CH 

load is not available, an indirect water heater can be used to 

dissipate the heat by creating a DHW call which will enable the 

DHW circulator.

 

 

5.

 

Press the RIGHT button to adjust the firing rate to 

100% (high fire). Hold down the RIGHT button to 

rapidly increase the firing rate.

 

6.

 

If the combustion levels during high fire are outside 

the recommended combustion settings (see Table 1), 

adjust the THROTTLE SCREW (see Fig. 7) using a flat- 

blade screwdriver as follows:

 

 

 

Counter-clockwise  adjustment  of  the  THROTTLE 

SCREW at High Fire (100% firing rate):

 

O

decreases and CO

2  

increases

 

Clockwise adjustment of the THROTTLE SCREW at 

High Fire (100% firing rate):

 

O

increases and CO

decreases

 

 

 

7.

 

Once the combustion level is set at high fire, manually 

place the boiler into low fire mode by pressing the 

LEFT button to adjust firing rate down to 1% (low 

fire).

 

 

8.

 

If the combustion level (O

2

 or CO

2

) during low fire is

 

 

 

 

 

 

 

 

Fig. 6:  CTRLMax Manual Operation

 

outside the recommended combustion settings in 

Table 1 contact Ideal USA Technical Support.

 

9.

 

Press  the  CENTER  button  while  the  fan  icon  is 

highlighted to shutdown the burner.

 

10.

 

Press the LEFT or RIGHT button to highlight the home 

screen icon to exit the service mode.

 

11.

 

Replace the front panel and put the boiler back into 

operation.

 

Manual  Operation

 

 

Released

 

CH1

 

DHW 

CH2

 

Off

 

Off 