19
British Gas 100 & 125 RD2 -
Installation & Servicing
INSTALLATION
FLUE OUTLET
23 CONNECTING THE FLUE TO THE BOILER - Rear
1.
Secure the flue to the boiler
using the three M5 wing nuts
provided.
Note.
The sealing ring studs will locate in
the back panel one way only. This
will ensure that the terminal is
correctly aligned.
1.
Secure the flue to the boiler, using the
three M5 wing nuts provided.
2.
Fit the kit extension tube (with ring) to the
flue elbow, rotate in the bayonet slot and
secure with the M4 screw.
3.
Engage the extension tube into the flue
outlet, connect the elbow to the fan outlet
and secure with the M4 screw.
Note.
The sealing ring studs will locate in the back
panel one way only. This will ensure that the
terminal is correctly aligned.
24 CONNECTING THE FLUE TO THE BOILER - Side
22 LOCATING THE BOILER
Rear and Side flue
A.
If the flue assembly can be fitted from the
outside
,
proceed as follows:
1.
Move the boiler into position ensuring that the flue
outlet is in line with the wall opening.
2.
Insert the flue assembly ensuring that the flue slides
into the flue extension and the 3 sealing ring studs
locate into the boiler.
B.
If the flue assembly has been fitted from the
inside
proceed as follows:
1.
Move the boiler into position ensuring that the flue
slides into the flue extension tube and the 3
sealing ring studs locate into the boiler back
panel.
Top flue
Position the boiler beneath the flue assembly.