KERS 50
–
Heat recovery ventilation unit
–
User & installation manual
© Ideal Clima
–
Page 9 / 28
Place upstream a circuit breaker with a higher nominal current than the sum of that required by all the devices
(see technical data table).
When multiple KERS are connected in series, all are managed from the first one (master) and its on board switches
or remote control. To connect in series the units together, connect the "output" terminal of the first KERS to the
terminal strip "input" of the second KERS. In the same way connect the second Kers to the next and so on, up to
a maximum of 10 units.
The first unit KERS (master) controls all the others. The units must be set in a way that half of them begin their cycle
in extraction, and the other half in supply phase, this way the rooms will not be subject to air pressure imbalances.
A series of dip-switch, located under the rubber end cap, allows to set such phases. (See chapter
“setting DIP
-
switch”).
5.
ON BOARD SWITCHES AND REMOTE CONTROL
The unit can be controlled with the on-board switches or with a remote control.
5.1
ON BOARD SWITCHES
Switches on the unit are located on the right side of the device. If you have installed multiple Kers, only the first
(“master”
) accepts the commands, either by switches or by remote control.
Control switches are capacitive type, so you will not need to push them.
Summary of Contents for KERS 50