37
Installation and Servicing
SECTION 2 - INSTALLATION
2.24 RESTART PROCEDURE
2.25 ACCESSING THE INSTALLER MODE
To access Installer Mode press the “PREHEAT” and “RESTART” Buttons
together for more than 5s.
1. The last 3 faults will be shown
See Section 4.1 for Fault Code descriptions
2. “SL” will be shown
To run the burner at minimum rate press “RESTART”, otherwise
press “PREHEAT”.
3. “SH” will be shown
To run the burner at maximum rate press “RESTART”, otherwise
press “PREHEAT”.
4. “VF” will be shown
To activate the venting function press “RESTART”, otherwise press
“PREHEAT”.
The venting function runs for 5 minutes before automatically
returning to normal operation
The diverter valve moves between CH and DHW every 30s
The Pump alternates between being on for 50s and then off for 10s
5. “dU” will be shown
To move the diverter valve to mid-position for replacement press
“RESTART”, otherwise press “PREHEAT”.
6. “P1” will be shown
To set the minimum CH pump speed to 100% press “RESTART”,
otherwise press “PREHEAT”.
7. “P7” will be shown
To set the minimum CH pump speed to 70% (default) press
“RESTART”, otherwise press “PREHEAT”.
8. “FL” will be shown
This feature is not required on this appliance. Press “PREHEAT”.
9. “SE” will be shown
This feature is not required on this appliance. Press “PREHEAT” to
exit.
Legend
A. Domestic Hot Water Temperature Knob
B. Central Heating Temperature Knob
C. Mode Knob
D. Boiler Status Display
E. Burner ‘on’ Indicator
F. Preheat On Off button
G. Restart button
H. Central Heating Economy Setting
J. Pressure Gauge
ºC
HOT WATER
PREHEAT
ON
MIN
MAX
MIN
MODE
e
BOILER
OFF
PREHEAT
RESTART
MAX
A
J
D
E
B
C
F
G
H
To restart the boiler, press the RESTART button (G).
INST
ALLA
TION
Summary of Contents for INDEPENDENT+ COMBI 24
Page 4: ...4 Installation and Servicing...
Page 6: ...6 Installation and Servicing...
Page 63: ...63 Installation and Servicing...
Page 64: ......
Page 70: ...70 NOTES Installation and Servicing...