CAutioN. 

 

to avoid the possibility of injury during the installation, servicing or cleaning of 

this appliance care should be taken when handling edges of sheet steel components.

All Gas Safe Registered Engineers carry a 

Gas Safe Register ID card, and have a registration number.  Both should 

be recorded in your Log Book. You can check your installer by calling 

Gas Safe Register direct on 0800 4085500

introduction

The 

xtra

 boilers are fully automatically controlled, floor 

standing

, fanned, super efficient condensing appliances.

Due to the very high efficiency, condensate is produced from the 

flue gases and this is drained to a suitable disposal point through 

the plastic waste pipe at the bottom of the boiler.  A condensate 

'plume' will also often be visible at the flue terminal.

safety

Current Gas Safety (installation & use) 

Regulations or rules in force.

In your own interest, and that of safety, it is the law that this boiler 

must be installed and maintained by a Gas Safe Registered 

Engineer or in IE a competent person, in accordance with the 

above regulations.

The appliance should be serviced at least once a year by a Gas 

Safe Registered Engineer or in IE a competent person.

It is essential that the instructions in this booklet are strictly 

followed, for safe and economical operation of the boiler.

electricity supply

The appliance must be earthed.

Supply 230 V - 50 Hz.    The fusing should be 7A for F320-F560.
This appliance is intended to be connected to the supply via two 

double-pole switches, having a 3mm contact separation in both 

poles, serving only the boiler and system controls. Alternatively, 

two 3-pin UNSWITCHED sockets may be used. 

important notes

  This appliance must not be operated without  

the casing correctly fitted.

•  Do not store objects around or on the boiler, and keep access 

clear at all times.

•  Do not obstruct ventilation ducts, grilles or openings in the 

boiler room, room space or compartment that the appliance is 

installed in, or the passage of combustion and ventilation to 

the boiler.

•  Do not turn off the boiler if it is to be left unattended in frosty 

weather.

•  If it is known or suspected that a fault exists on the boiler then 

it MUST NOT BE USED

 until the fault has been corrected by a 

Gas Safe Registered Engineer or in IE a competent person.

•  Flammable materials must not be placed in close proximity to 

the appliance. Materials giving off flammable vapours must not 

be stored in the same room as the appliance.

In cases of repeated or continuous shutdown a Gas Safe 

Registered Engineer or in IE a competent person should be called 

to investigate and rectify the condition causing this and carry out 

an operational test after each intervention on the device. Only the 

manufacturers original parts should be used for replacement.

minimum Clearances

Rear:

1000mm or adequate space from the rear of the jacket to make 

the flue connections and access to the flue sample point, drain 

connection, flue and any safety or control devices.

Left Side:

450mm.

Right Side:

450mm.

Front:

600mm; except, access doors may be closer, but not less than 

200mm and 600mm must still be available for service across the 

width of the boiler.

top:

500mm.

to light the boiler  

(Refer to Frame 1)

1. 

CHECK THAT THE ELECTRICITY SUPPLY TO THE BOILER 

IS OFF.

2.

  Set the burner on/off switch (A) to off.

3.

  Switch on the electricity supply to the boiler and check that all 

external controls, e.g. programmer, room thermostat etc. are 

on.  Allow the boiler to carry out a self check.

4.

  Set the burner on/off switch (A) to ON.

The boiler will commence the ignition sequence, supplying heat to 

the system when required.

xtra

Natural Gas only
Pi No.  

0063 BR 3123

Destination Countries:  

GB,  

IE

2

202863-8.indd   62

18/10/2010   08:46:16

Summary of Contents for Imax xtra F320

Page 1: ...en replacing any part on this appliance use only spare parts that you can be assured conform to the safety and performance specification that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers xtra Models F320 F400 F480 F560 xtra ...

Page 2: ...tted Do not store objects around or on the boiler and keep access clear at all times Do not obstruct ventilation ducts grilles or openings in the boiler room room space or compartment that the appliance is installed in or the passage of combustion and ventilation to the boiler Do not turn off the boiler if it is to be left unattended in frosty weather If it is known or suspected that a fault exist...

Page 3: ...fcheck i e the DHW valve if connected is energised first for 15 seconds then the CH pump is switched on for a further 10 seconds This cycle repeats itself every 24hrs as long as no heat request is given in 24hrs Burner on off Switch With the burner switch set to off the boiler will not respond to a CH demand However it will respond to a DHW demand and the pump anti seize and frost protection modes...

Page 4: ... case a separate frost protection should be fitted Boiler Overheat Boiler overheating is detected by electrical sensors connected to the boiler control module If the boiler overheats it will shut down and the display will show E18 Press the reset button D and the boiler will relight If the fault recurs turn off the boiler and consult a Gas Safe Registered Engineer or in IE a competent person Conde...