CAutioN.
to avoid the possibility of injury during the installation, servicing or cleaning of
this appliance care should be taken when handling edges of sheet steel components.
All Gas Safe Registered Engineers carry a
Gas Safe Register ID card, and have a registration number. Both should
be recorded in your Log Book. You can check your installer by calling
Gas Safe Register direct on 0800 4085500
introduction
The
xtra
boilers are fully automatically controlled, floor
standing
, fanned, super efficient condensing appliances.
Due to the very high efficiency, condensate is produced from the
flue gases and this is drained to a suitable disposal point through
the plastic waste pipe at the bottom of the boiler. A condensate
'plume' will also often be visible at the flue terminal.
safety
Current Gas Safety (installation & use)
Regulations or rules in force.
In your own interest, and that of safety, it is the law that this boiler
must be installed and maintained by a Gas Safe Registered
Engineer or in IE a competent person, in accordance with the
above regulations.
The appliance should be serviced at least once a year by a Gas
Safe Registered Engineer or in IE a competent person.
It is essential that the instructions in this booklet are strictly
followed, for safe and economical operation of the boiler.
electricity supply
The appliance must be earthed.
Supply 230 V - 50 Hz. The fusing should be 7A for F320-F560.
This appliance is intended to be connected to the supply via two
double-pole switches, having a 3mm contact separation in both
poles, serving only the boiler and system controls. Alternatively,
two 3-pin UNSWITCHED sockets may be used.
important notes
•
This appliance must not be operated without
the casing correctly fitted.
• Do not store objects around or on the boiler, and keep access
clear at all times.
• Do not obstruct ventilation ducts, grilles or openings in the
boiler room, room space or compartment that the appliance is
installed in, or the passage of combustion and ventilation to
the boiler.
• Do not turn off the boiler if it is to be left unattended in frosty
weather.
• If it is known or suspected that a fault exists on the boiler then
it MUST NOT BE USED
until the fault has been corrected by a
Gas Safe Registered Engineer or in IE a competent person.
• Flammable materials must not be placed in close proximity to
the appliance. Materials giving off flammable vapours must not
be stored in the same room as the appliance.
In cases of repeated or continuous shutdown a Gas Safe
Registered Engineer or in IE a competent person should be called
to investigate and rectify the condition causing this and carry out
an operational test after each intervention on the device. Only the
manufacturers original parts should be used for replacement.
minimum Clearances
Rear:
1000mm or adequate space from the rear of the jacket to make
the flue connections and access to the flue sample point, drain
connection, flue and any safety or control devices.
Left Side:
450mm.
Right Side:
450mm.
Front:
600mm; except, access doors may be closer, but not less than
200mm and 600mm must still be available for service across the
width of the boiler.
top:
500mm.
to light the boiler
(Refer to Frame 1)
1.
CHECK THAT THE ELECTRICITY SUPPLY TO THE BOILER
IS OFF.
2.
Set the burner on/off switch (A) to off.
3.
Switch on the electricity supply to the boiler and check that all
external controls, e.g. programmer, room thermostat etc. are
on. Allow the boiler to carry out a self check.
4.
Set the burner on/off switch (A) to ON.
The boiler will commence the ignition sequence, supplying heat to
the system when required.
xtra
Natural Gas only
Pi No.
0063 BR 3123
Destination Countries:
GB,
IE
2