46
icos system condensing -
Installation and Servicing
F
AUL
T FINDING F
AUL
T FINDING F
AUL
T FINDING F
AUL
T FINDING
FAULT FINDING
Does the pump setting give a differential
across the boiler in excess of 25
o
C
Can the overheat condition be reset by pressing
the boiler reset button when the system is cold ?
Replace the system pump
Set CH control knob to maximum.
If the overheat trips again measure the flow temp:
Over 90
o
C
Check control thermistor
(
Refer to Frame 79)
.
Under 90
o
C
Replace overheat 'stat
YES
YES
Check that the pump is rotating freely.
Is differential now below 25
o
C ?
NO
NO
77 L.......A......................... (OVER HEAT SENSOR)
Fill and vent the system and open all
isolation valves
YES
Is the boiler and CH system filled with
water and all isolation valves open ?
OK
NO
YES
NO
Replace overheat thermostat
78 L....8.....
(FAN)
Is nominal 330 V DC present
across red and blue at the fan
connector as reset button is
pressed?
Replace fan
YES
NO
Replace harness
79 H.....1..... (CONTROL TEMPERATURE SENSOR)
YES
Is there continuity between the
PCB and the thermistor ?
Check resistance. The sensors can be
checked by measuring their resistance, using
a suitable multimeter connected across the
sensors' terminal pins
At 25
o
C
expect
9,700-10,300 Ohms
At 60
o
C
expect
2,400-2,600 Ohms
At 85
o
C
expect
1,000-1,100 Ohms
Remove the boiler control thermistor from the
CH flow pipe and disconnect thermistor wires.
Are the thermistor values correct ?
Replace the thermistor
NO
NO
YES
Replace PCB
Check and replace wiring as necessary
Replace PCB
YES
Is 14V DC present
across yellow and pink
at the fan connector?
Check wiring harness for
continuity. Is there continuity?
NO
YES
NO