3
Concord CXSD/H -
Installation & Servicing
GENERAL
CAUTION.
To avoid the possibility of injury during the installation, servicing or cleaning of
this appliance, care should be taken when handling edges of sheet steel components.
CONTENTS
Air Supply
. .........................................................................
8
Boiler Assembly - exploded view
. ....................................
9
Boiler Clearances
. ............................................................
5
Burner Assemblies - exploded views
. ..............................
CXSD 40/H-90/H
. ........................................................
26
CXSD 100/H-120/H
.....................................................
27
Casing Assembly
. ...........................................................
12
Chimney System
. ..............................................................
8
Commissioning
. ..............................................................
17
Controls
. ............................................................................
4
Electrical Connections
. ..................................................
14
Electrical Supply
. ..............................................................
8
Fault Finding
. ...................................................................
32
Gas Safety Regulations
....................................................
3
Gas Supply
. ........................................................................
8
Hydraulic Resistance
. ......................................................
5
Initial Lighting
. .................................................................
17
Installation
. ........................................................................
9
Mandatory Requirements
. ...............................................
7
Option Kits
. ........................................................................
4
Pump
. ................................................................................
6
Servicing
. ........................................................................
24
Short List of Parts
. .........................................................
35
Site Assembled Boilers
. .................................................
30
Static Head Requirements
. ..............................................
6
System Connections
. .....................................................
11
Ventilation
. ........................................................................
8
Water Circulation
. ............................................................
4
Water Connections
. .........................................................
4
Water Treatment
. .............................................................
6
Wiring Diagrams
. ............................................................
15
Concord CXSD 40/H - 120/H
(Natural gas)
B.G. Certified
-
P.I. No
. 87/AQ/103
Destination Countries:
GB & IE
INTRODUCTION
CONSTRUCTION
Boiler body
The sectional boiler body is of cast iron and is supplied assembled
on a sheet steel combustion chamber with an integral draught
diverter. The boiler can be supplied in sectioned form to special
order for site assembly - refer to the section headed ‘Instructions
for Site Assembled Boilers’.
Casing
The casing is manufactured in stove enamelled sheet steel and
is easily assembled on site.
Burners
The 3 burners are of stainless steel construction.
Current Gas Safety (Installation and Use)
Regulations or rules in force.
It is the law that
all
gas appliances are installed and serviced by
a CORGI registered installer in accordance with the above
regulations. Failure to install appliances correctly could lead to
prosecution. It is in your own interest, and that of safety, to ensure
that the law is complied with.
The
Concord CXSD 40/H-120/H
range of boilers has been tested
and certified by British Gas to prEN656 for use with
Natural gas
only.
Multiple boiler installations
The
Concord CXSD/H
range is certificated for use in multiple
boiler installations, providing that the following conditions are
satisfied.
1.
A downdraught thermostat kit MUST be fitted to ALL boilers
in the installation.
2.
A maximum of 6 boilers may be used with a single flue
header.
3.
For clearances see Frame 2.
A comprehensive guide to multiple installations of Concord
CXSD/H boilers is available.
WARNING.
Failure to use a downdraught kit on every boiler in
a multiple boiler installation will negate the certification of the
installation and therefore contravene the essential requirements
of the Gas Appliance Directive.
Note.
The
CXSD 40/H,
CXSD 50/H and CXSD 60/H
boilers are
intended for use as commercial boilers and are NOT certified for
use in domestic applications. A domestic installation is defined
as an installation where the boiler takes its combustion air from
a living space or from a room directly or indirectly connected with
the living space. It is important, therefore, that no external control
devices - e.g. flue dampers, economisers etc., are directly
connected to this appliance unless covered by these Installation
and Servicing Instructions or otherwise recommended by
Caradon Ideal Limited
in writing. If in doubt please enquire.
Any direct connection of a control device not approved by
Caradon
Ideal Limited
could invalidate the British Gas Certification, the
normal appliance warranty and could also infringe the Gas Safety
Regulations. Table 1, Table 2 and the descriptive notes which
follow contain all the essential data likely to be required by the
installer.