background image

TITAN ELITE CEILING & WALL MOUNT INsTALL

TITAN ELITE INSTALLATION - 09/01/16 pjm

Page 1 of 4

Do not use power tools to assemble or 

adjust the arm. Use hand tools onLY.

IMPORTANT

ICW recommends wood or metal stud mounting only. 

MAXIMUM LOAD CAPACITY: 

28 Lbs (12.7 kg)

• 

Do not

 attempt to adjust the arm until all components 

are mounted (monitor, keyboard, etc.)

• 

Arm must be completely horizontal 

(extended) 

before adjusting the arm’s tension. Failure to do so will 

damage the arm and void the warranty.

• 

never loosen or remove any of the shoulder 

bolts.

 Doing so will cause the arm to immediately 

come apart with tremendous force, and could cause 

serious injury.

• 

If equipment requiring AC power is mounted to this unit, 

have a certified electrician inspect the installation.

• 

Failure to install this unit according to these instructions 

will void all ICW warranties. If installed incorrectly, ICW 

is not liable for any damage or injury caused by the unit.

the elite arm contains high pressure gas 

springs. the following cautions MUSt be 

observed to avoid serious injury.

DANGER!

MOUNT sQUARE CEILING PLATE

Loosen the set screw 

in ceiling plate before 

attaching extension pipe.

Using four 1/4 x 2” lag bolts 

provided in hardware bag, 

secure ceiling plate to a solid 

wood surface or ceiling joist. 

Use square pattern or inline 

pattern. Be sure to use all four 

bolts. 
Run wires through center hole 

or wire management port. 

Loosen set screw BEFORE 

attaching pipe. Screw 

extension pipe into ceiling 

plate, then tighten set screw.

Wire management holes

MOUNT INLINE CEILING PLATE

Loosen the set screw 

in ceiling plate before 

attaching extension pipe.

Firmly secure ceiling mount 

to solid ceiling joist using 

four #14 wood screws found 

in hardware bag. Be sure 

mount is level. 
Loosen set screw BEFORE 

attaching pipe. Screw extension pipe into ceiling 

plate, then tighten set screw.

Ceiling Mount

Wall Mount

MOUNT WALL EAR & PLATE

Using the 3/16 hex key 

provided, attach wall plate 

to ear with four 1/4-20 

screws provided.

Locate stud and mark top 

hole, drill 11/64 pilot hole 

and insert #14 screw and 

tighten slightly. Using a 

level, mark lower holes and 

drill pilot holes. Insert #14 

screws and, with unit level, 

tighten all screws.

NOTE: ICW supplies #14 

wood screws. If installing 

onto metal studs, you will 

need to replace with proper 

metal stud fasteners.

Thread arm onto extension pipe 

and tighten. AFTER arm is firmly 

attached, tighten set screw with 

5/32 hex key.

DO NOT loosen lower, smaller screw 

without instructions from ICW.

ATTACH ARM TO EXTENsION PIPE

Set 

screw

Summary of Contents for TITAN ELITE

Page 1: ... four 1 4 x 2 lag bolts provided in hardware bag secure ceiling plate to a solid wood surface or ceiling joist Use square pattern or inline pattern Be sure to use all four bolts Run wires through center hole or wire management port Loosen set screw BEFORE attaching pipe Screw extension pipe into ceiling plate then tighten set screw Wire management holes MOUNT INLINE CEILING PLATE Loosen the set sc...

Page 2: ...G TO PARALINK ATTACH FLIP UP Remove screws from drop extension using 5 32 hex key Align holes in keyboard tray with screw holes in drop extension Attach keyboard tray using the provided screws ATTACH PARALINK Remove beauty cap on Paralink Remove screw using 3 16 hex key Slide keyboard tray into Paralink Replace screw and tighten Replace beauty cap Beauty cap Screw Attach the Paralink Keyboard Moun...

Page 3: ... in Elite arm end covers Reassemble arm and reattach covers Note When measuring for length of cords be sure to allow enough extra cord to accommodate tilt and rotation of monitor NOTE CORDS CAN BE DAMAGED IF JOINTS ARE ROTATED MORE THAN 360 DEGREES USE ROTATION STOP PINS TO AVOID DAMAGE Rotation Bearing Rotation Bearing End cap End cover End cover Top cover Titan Arm Wire Management Detail ADJUST ...

Page 4: ...s head screwdriver Torque Chart In lbs 2 23 2016 Minimum torque values Monitor Mount Arm Base Mount Arm Joint Paralink EV710 Ultra 0 2 1 0 2 1 0 2 1 e t i l E 0 2 1 0 2 1 0 2 1 0 2 1 e t i l E 2 T Titan T2 120 120 120 120 0 2 1 5 8 0 2 1 0 2 1 0 2 1 a r t l U UL180 UL182 120 120 85 MD Arm 140 120 120 Feed monitor and other cords and any other cords down through the ceiling extension pipe Slip all ...