28
PRX-TSEC
tSec Multi-Technology Card Reader
Installation Manual | June 2017
12
UL and ULC Installation Requirements
i
Only UL / ULC listed compatible products are intended to be connected to a UL / ULC listed access
control system.
12.1
CAN/ULC-S319-05
This card reader is CAN/ULC-S319 Listed for Class I applications only.
Exit devices and wiring must be installed within the protected area.
The card reader must be connected with shielded, grounded cable.
Fail secure locking mechanism shall only be installed where allowed by the local authority having jurisdiction
(AHJ) and shall not impair the operation of panic hardware and emergency egress.
If fire resistance is required for door assembly, portal locking device(s) must be evaluated to ULC-S533 and
CAN/ULC-S104.
Must be installed with CAN/ULC-S319 Listed portal locking device(s) for ULC installations.
Input power must be supplied by a Class 2 or power limited device.
12.2
UL294
This card reader is UL 294 Listed for Class 1 applications only.
Exit devices and wiring must be installed within the protected area.
The card reader must be connected with shielded, grounded cable.
Fail secure locking mechanism shall only be installed where allowed by the local authority having jurisdiction
(AHJ) and shall not impair the operation of panic hardware and emergency egress.
If fire resistance is required for door assembly, portal locking device(s) must be evaluated to UL10B or
UL10C.
Must be installed with UL 1034 Listed electronic locks for UL installations.
Input power must be supplied by a Class 2 or power limited device.