background image

Mounting

Protege DIN rail modules are designed to mount on standard DIN rail either in dedicated DIN cabinets or on
generic DIN rail mounting strip.

When installing a DIN rail module, ensure that there is adequate clearance around all sides of the device and
that air flow to the vents of the unit is not restricted. It is recommended that you install the module in a location
that will facilitate easy access for wiring. It is also recommended that the module is installed in an electrical
room, communication equipment room, secure cabinet, or in an accessible area of the ceiling.

1.

Position the DIN rail module with the labeling in the correct orientation.

2.

Hook the mounting tabs (opposite the tab clip) under the edge of the DIN rail.

3.

Push the DIN rail module against the mount until the tab clips over the rail.

Removal

A Protege DIN rail module can be removed from the DIN rail mount using the following steps:

1.

Insert a flat blade screwdriver into the hole in the module tab clip.

2.

Lever the tab outwards and rotate the unit off the DIN rail mount.

PRT-ZX16-DIN | Protege DIN Rail 16 Input Expander | Installation Manual

9

Summary of Contents for PRT-ZX16-DIN

Page 1: ...PRT ZX16 DIN Protege DIN Rail 16 Input Expander Installation Manual ...

Page 2: ...or mechanical for any purpose without the express written permission of Integrated Control Technology Limited Designed and manufactured by Integrated Control Technology Limited Protege and the Protege Logo are registered trademarks of Integrated Control Technology Limited All other brand or product names are trademarks or registered trademarks of their respective holders Copyright Integrated Contr...

Page 3: ...tors 16 Error Code Indication 17 Error Code Display 17 Mechanical Diagram 18 Mechanical Layout 19 Technical Specifications 20 New Zealand and Australia 21 European Standards 22 UL and ULC Installation Requirements 24 UL ULC Installation Cabinet Options 24 Central Station Signal Receiver Compatibility List 24 ULC Compliance Requirements 25 CAN ULC S304 25 CAN ULC S559 27 UL Compliance Requirements ...

Page 4: ...Disclaimer and Warranty 35 PRT ZX16 DIN Protege DIN Rail 16 Input Expander Installation Manual 4 ...

Page 5: ...o be connected to the RS 485 module network Up to 250 modules can be connected to the Protege system in any combination to the network over a distance of up to 900M 3000ft Further span can be achieved with the use of a network repeater module The current features of the input expander include Secure encrypted RS 485 module communications 16 inputs Industry standard DIN rail mounting Online and rem...

Page 6: ...Burglar Alarm Systems CAN ULC S302 Installation and Classification of Burglar Alarm Systems for Financial and Commercial Premises Safes and Vaults CAN ULC S561 Installation and Services for Fire Signal Receiving Centres and Systems The National Electrical Code ANSI NFPA 70 The Canadian Electrical Code Part I CSA C22 1 AS NZS 2201 1 Intruder Alarm Systems The Local Authority Having Jurisdiction AHJ...

Page 7: ... copper wire or wires of the appropriate gauge Earth Ground Connection The DIN rail enclosure and the DIN rail modules must be grounded to a suitable single point earth ground connection in the installation A minimum 14AWG solid copper wire or thicker in accordance with local authorities shall be used from the Protege system s earth connection points The DIN rail enclosure includes an earth ground...

Page 8: ...ound Link Connection DIN Rail Enclosure DIN Rail Enclosure DIN Rail Enclosure Module Network RS 485 N N NA and NB DIN Rail Ground Connections multiple cabinets in different rooms sectors or buildings Note that the DIN rail enclosure earth terminal is connected to the power supply V terminal There must be only one single earth grounding point per system PRT ZX16 DIN Protege DIN Rail 16 Input Expand...

Page 9: ...is installed in an electrical room communication equipment room secure cabinet or in an accessible area of the ceiling 1 Position the DIN rail module with the labeling in the correct orientation 2 Hook the mounting tabs opposite the tab clip under the edge of the DIN rail 3 Push the DIN rail module against the mount until the tab clips over the rail Removal A Protege DIN rail module can be removed...

Page 10: ...m Controller or module supplying power to networked devices Next modules on network B N N N A N White Blue Black Red Input Expander CAUTION INCORRECT WIRING MAY RESULT IN DAMAGE TO THE UNIT Value 1 Value 2 Monitored Status 1K 1K Open Close Tamper Short 6K8 2K2 Open Close Tamper Short 10K 10K Open Close Tamper Short 2K2 2K2 Open Close Tamper Short 4K7 2K2 Open Close Tamper Short 4K7 4K7 Open Close ...

Page 11: ...d voltage to all devices on the RS 485 network Warning The 12V N and N communication input must be supplied from only one point Connections from more than one 12V supply may cause failure or damage to the unit or the device supplying network power The 330 ohm EOL End of Line resistor provided in the accessory bag must be inserted between the NA and NB terminals of the first and last modules on the...

Page 12: ...ith the EOL resistor configuration the controller generates an alarm condition when the state of an input changes between open and closed and generates a tamper alarm condition when a wire fault short circuit or a cut wire tampered in the line occurs When using the EOL resistor configuration the EOL resistor option must be enabled in the input programming so that the tamper and short states can be...

Page 13: ...The following table details the trouble inputs that are configured in the system and the trouble type and group that they activate Input Number Description Type Group ZXxxx 01 15 Reserved None None ZXxxx 16 Module Offline Module Offline System Replace xxx with the appropriate address of the module that you are programming PRT ZX16 DIN Protege DIN Rail 16 Input Expander Installation Manual 13 ...

Page 14: ...n the product Refer to the Protege system controller installation manual for address programming details The controller has a set limit on the number of modules of each type that it can support When adding and configuring modules always refer to the Maximum Module Addresses table in the controller installation manual PRT ZX16 DIN Protege DIN Rail 16 Input Expander Installation Manual 14 ...

Page 15: ...odule update or the identification time period expiring the module will return to normal operation Fault Indicator The fault indicator is lit any time the module is operating in non standard mode If the fault indicator is flashing the module requires a firmware update or is in firmware update mode When the fault indicator is on the status indicator will flash an error code State Description Contin...

Page 16: ... test verification of inputs without the need to view the inputs from the keypad or the Protege software State Description Constantly off Input is not programmed Constantly on red Input is in an open state Constantly on green Input is in a closed state Continuous flash red Input is in a tamper state Continuous flash green Input is in a short state PRT ZX16 DIN Protege DIN Rail 16 Input Expander In...

Page 17: ...pdate feature in the controller s web interface 3 Address Too High The module address is above the maximum number available on the system controller To clear this error change the address to one within the range set on the system controller restart the module by disconnecting the power 4 Address In Use The address is already in use by another module To clear this error set the address to one that ...

Page 18: ...Diagram The mechanical diagram shown below outlines the essential details needed to help ensure the correct installation of the input expander PRT ZX16 DIN Protege DIN Rail 16 Input Expander Installation Manual 18 ...

Page 19: ...ial details needed to help ensure correct installation and mounting All measurements are shown in millimeters 90 00 156 80 44 68 Front 139 18 72 00 2x 4 67 Screw Hole 17 03 42 40 42 40 156 80 35 40 Back PRT ZX16 DIN Protege DIN Rail 16 Input Expander Installation Manual 19 ...

Page 20: ...131 F Storage Temperature 10 to 85 C 14 to 185 F Humidity 0 93 non condensing indoor use only relative humidity Mean Time Between Failures MTBF 784 316 hours calculated using RFD 2000 UTE C 80 810 Standard The total combined current refers to the current that will be drawn from the external power supply to supply the expander and any devices connected to its outputs The auxiliary outputs are direc...

Page 21: ...alia General Product Statement The RCM compliance label indicates that the supplier of the device asserts that it complies with all applicable standards PRT ZX16 DIN Protege DIN Rail 16 Input Expander Installation Manual 21 ...

Page 22: ... waste handling Please contact your local authority for further details of your nearest designated collection point Penalties may be applicable for incorrect disposal of this waste in accordance with your national legislation For business users in the European Union If you wish to discard electrical and electronic equipment please contact your dealer or supplier for further information Information...

Page 23: ... detector per input Do not mix unpowered detectors and non latching powered detectors on an input To comply with EN 50131 1 the Entry Timer should not be programmed to more than 45 seconds To comply with EN 50131 1 the Bell Cut Off Time should be programmed between 02 and 15 minutes EN 50131 1 requires that detector activation LEDs shall only be enabled during Walk Test This is most conveniently a...

Page 24: ...ULC ORD C1076 86 CAN ULC S319 EN DIN 31 EN DIN 24 EN DIN 24 ATTACK P UL ULC All cabinet installations of this type must be located inside the Protected Area Not to be mounted on the exterior of a vault safe or stockroom All cabinet internal covers and lids doors must be connected to the cabinet s main ground point for electrical safety and static discharge protection Central Station Signal Receive...

Page 25: ...ible with the ArmorIP Internet Monitoring Receiver Poll Time must be set to 40 seconds and the Grace Time must be set to 20 seconds In the Protege system the reporting service must be configured to 40 seconds The following options are required for the service selected as Report IP type The Log Polling Message option must be enabled Refer to the section Report IP Options in the Operator Reference M...

Page 26: ...e Trouble Input Area must be armed Refer to the section Trouble Inputs Areas and Input Types in the Operator Reference Manual The Log Modem Events to Event Buffer option must be selected in the Contact ID Reporting Service Network and Domain Access Neither the subscriber control unit nor the signal receiving center receiver shall be susceptible to security breaches in general purpose operating sys...

Page 27: ...rIP detects the reception of any invalid packet on the programmed port as a potential system compromise attempt Each compromise attempt sends a notification to the receiver and logs a Compromise Attempt event under the Live Panel Events The event is sent with the following details Account Code as defined in the Serial Receiver settings Event Code 0x163 Group Code as defined in the Serial Receiver ...

Page 28: ...nual Check In Time DACT communication channel check in time is not to exceed 24 hrs Trouble Input Service Test Report The Test Report Time must be programmed Refer to the section Controllers Configuration in the Operator Reference Manual The Generate Input Restore on Test Input option must be enabled Refer to the section Controller Options in the Operator Reference Manual The Test Report Time is P...

Page 29: ... Open1ivlose1iTamper1iShort K K Open1ivlose1iTamper1iShort ZgUX3 Z5 vOM vOM Z Z0 Z NXvi Tamper NXviInputivontact Valuei Valuei5 AiFireiareasishallibeiseparatedifromiburglariareasithroughiareaipartitioningX AiFireiInputsiZ53Z0ishallibeiusediexclusivelyiforifireimonitoringiandicannotibeiprogrammeditoiactivateitheibellioutput ULvicertifiedi5 Vi viPoweriSupply Z 3 5 V v 5 V v gUX Z 3 Z 3 5 V v Z 3 s s...

Page 30: ...itoiactivateitheibellioutput AFireiInputiZ iNXOiPushi uttonitoibeiusediasimonitoringiresetiswitchX NXx Tamper NXxiInputixontact Valuei Valuei5 TypicaliInputixircuits EOL Resitor Input Configuration Fire area inputs must be programmed as follows FACP Fire Alarm Signal input type must be programmed as Fire Supervisory Trouble Signal input type must be programmed as 24 HR Silent Trouble Signal input ...

Page 31: ...he Operator Reference Manual When more than one means of signal transmission is used loss of communication with the receiving system shall be annunciated at the receiver within 200 seconds If a fault is detected on any of the signal transmission means at least one of the signal transmission channels shall send a signal to the central station to report the fault within 200 seconds The Report IP and...

Page 32: ... compromise attempt sends a notification to the receiver and logs a Compromise Attempt event under the Live Panel Events The event is sent with the following details Account Code as defined in the Serial Receiver settings Event Code 0x163 Group Code as defined in the Serial Receiver settings Point Code as defined in the Serial Receiver settings Refer to the section Global Settings Serial Receiver ...

Page 33: ... This device may not cause harmful interference This device must accept any interference received including interference that may cause undesired operation NOTE THE GRANTEE IS NOT RESPONSIBLE FOR ANY CHANGES OR MODIFICATIONS NOT EXPRESSLY APPROVED BY THE PARTY RESPONSIBLE FOR COMPLIANCE SUCH MODIFICATIONS COULD VOID THE USER S AUTHORITY TO OPERATE THE EQUIPMENT PRT ZX16 DIN Protege DIN Rail 16 Inp...

Page 34: ...ent ICES 003 This is a Class A digital device that meets all requirements of the Canadian Interference Causing Equipment Regulations CAN ICES 3 A NMB 3 A PRT ZX16 DIN Protege DIN Rail 16 Input Expander Installation Manual 34 ...

Page 35: ...hall be liable under any circumstances to any party in respect of decisions or actions they may make as a result of using this information In accordance with the ICT policy of enhanced development design and specifications are subject to change without notice For warranty information see our Standard Product Warranty PRT ZX16 DIN Protege DIN Rail 16 Input Expander Installation Manual 35 ...

Page 36: ...reserved Disclaimer Whilst every effort has been made to ensure accuracy in the representation of this product neither Integrated Control Technology Ltd nor its employees shall be liable under any circumstances to any party in respect of decisions or actions they may make as a result of using this information In accordance with the ICT policy of enhanced development design and specifications are s...

Reviews: