The ComNet FDW1000 Series and EXP101 Series of transceivers makes it possible to 
install card readers farther from the access control panel by providing a long-range 
fiber optic connection between the door or gate readers and most manufacturers’ 
access control panels.  The series includes both a remote (door/gate) device and a 
central (access control panel) device.  The FDW1000 devices are compatible with the 
EXP101 expansion modules that allow up to seven additional readers to share the 
optical link created by the FDW1000/C (central) and FDW1000/R (remote) devices.

This manual serves the following 

ComNet Model Numbers:

FDW1000M/C 
FDW1000M/R
FDW1000S/C
FDW1000S/R
EXP101/C
EXP101/R
EXP100/C
EXP100/R

Summary of Contents for EXP100C

Page 1: ...ptic connection between the door or gate readers and most manufacturers access control panels The series includes both a remote door gate device and a central access control panel device The FDW1000 devices are compatible with the EXP101 expansion modules that allow up to seven additional readers to share the optical link created by the FDW1000 C central and FDW1000 R remote devices This manual se...

Page 2: ...Preparation 5 Tools 5 Before beginning 5 Configuring Devices 6 Configuring an FDW1000 current version rev 3xx range 7 Configuring an EXP101 current version rev 4xx range 9 Configuring an FDW1000 C old version rev 2xx range 10 Configuring an FDW1000 R old version rev 2xx range 12 Configuring an EXP100 old version rev 3xx range 14 Wiring and Wiring Examples 15 Recommendations for new wire installati...

Page 3: ...acturers access control panels The series includes both a remote door gate device and a central access control panel device The FDW1000 devices are compatible with the EXP101 expansion modules that allow up to seven additional readers to share the optical link created by the FDW1000 C central and FDW1000 R remote devices Items in this series FDW1000M C Wiegand transceiver central side multimode FD...

Page 4: ... and EXP101 C central units will each accept up to two dry contact closures as inputs RELAY 1 IN and RELAY 2 IN and pass the status of each contact to corresponding FDW1000 R and EXP101 R remote units each containing two single pole double throw relays RELAY 2 OUT and RELAY 2 OUT Relay Channels 3 and 4 FDW1000 R and EXP101 R remote unit will each accept up to two dry contact closures as inputs REL...

Page 5: ...asi Rusco systems determine the number of expansion module pairs if any that will be needed this quantity will be one less than the number of readers in the link determine whether Relay 3 will be reserved to monitor the status of the optical link locate the STATUS indicator LED between the 2 pin power connector and the 8 pin terminal strip see Figures 1 and 2 below with the cover removed locate th...

Page 6: ...e range Initialization and programming for the two ranges differ as well Instructions for the two ranges are included with this document Current version expansion modules are labeled EXP101 C or EXP101 R and have revision designa tions in the 4xx range The older versions of the expansion modules are labeled EXP100 instead of EXP101 and have revision designations in the 3xx range Old EXP100s and ne...

Page 7: ...t DIP Switch 6 DIP Switch 7 DIP Switch 8 not used during initialization OFF OFF OFF Wiegand OFF OFF ON Wiegand no filter OFF ON OFF strobed rising edge MR 5 OFF ON ON strobed rising edge Dorado 644 ON OFF OFF strobed rising edge Mag Tek ON OFF ON strobed falling edge ON ON OFF unsupervised F 2F ON ON ON Apply power to the FDW1000 The STATUS indicator LED near the power connector should very quickl...

Page 8: ...lows Relay Channel 3 to be used to monitor the status of the optical link 5 Pull Up Resistor OFF disables pull up resistor ON enables pull up resistor for copper paths 200 ft or when using F 2F Casi Rusco 941 6 7 and 8 Number of EXP101 Pairs OFF OFF OFF no expansion modules OFF OFF ON one pair of expansion modules OFF ON OFF two pairs of expansion modules OFF ON ON three pairs of expansion modules...

Page 9: ...F ON strobed falling edge ON ON OFF unsupervised F 2F ON ON ON Using DIP Switches 6 7 and 8 set the polling address of each pair of EXP101s using the table below If only one pair of EXP101s will be used set the EXP101 C and the EXP101 R to polling address 1 If more than one pair of EXP101s will be used set one pair of EXP101 C and EXP101 R to polling address 1 Address the next pair using polling a...

Page 10: ...next pair using polling address 2 and continue sequentially as needed Number of EXP100 Pairs DIP Switch 6 DIP Switch 7 DIP Switch 8 no EXP100 pairs OFF OFF OFF one pair of EXP100s polling address 1 OFF OFF ON two pairs of EXP100s polling address 2 OFF ON OFF three pairs of EXP100s polling address 3 OFF ON ON four pairs of EXP100s polling address 4 ON OFF OFF five pairs of EXP100s polling address 5...

Page 11: ...ogramming OFF OFF OFF Wiegand OFF OFF ON Wiegand no filter OFF ON OFF strobed rising edge MR 5 OFF ON ON strobed rising edge Dorado 644 ON OFF OFF strobed rising edge Mag Tek ON OFF ON strobed falling edge ON ON OFF unsupervised F 2F ON ON ON Apply power to the FDW1000 C The device is now ready to use A common ground connection is critical for proper operation At each remote location a common grou...

Page 12: ...next pair using polling address 2 and continue sequentially as needed Number of EXP100 Pairs DIP Switch 6 DIP Switch 7 DIP Switch 8 no EXP100 pairs OFF OFF OFF one pair of EXP100s polling address 1 OFF OFF ON two pairs of EXP100s polling address 2 OFF ON OFF three pairs of EXP100s polling address 3 OFF ON ON four pairs of EXP100s polling address 4 ON OFF OFF five pairs of EXP100s polling address 5...

Page 13: ...ogramming OFF OFF OFF Wiegand OFF OFF ON Wiegand no filter OFF ON OFF strobed rising edge MR 5 OFF ON ON strobed rising edge Dorado 644 ON OFF OFF strobed rising edge Mag Tek ON OFF ON strobed falling edge ON ON OFF unsupervised F 2F ON ON ON Apply power to the FDW1000 R The device is now ready to use A common ground connection is critical for proper operation At each remote location a common grou...

Page 14: ...to make the unit an EXP100 R Remote unit Using DIP Switches 6 7 and 8 set the polling address of each pair of EXP100s using the table below If only one pair of EXP100s will be used set the EXP100 C and the EXP100 R to polling address 1 If more than one pair of EXP100s will be used set one pair of EXP100 C and EXP100 R to polling address 1 Address the next pair using polling address 2 and continue ...

Page 15: ...25 feet max Wiegand LED PVC Belden 9942 or 8777 22 AWG 3 pair shielded 250 feet max Plenum Belden 82777 22 AWG 3 pair shielded 250 feet max PVC Belden 9873 20 AWG 3 pair shielded 500 feet max Plenum Belden 83606 or 85164 20 AWG 3 pair shielded 500 feet max Inputs and Outputs PVC Belden 8451 22 AWG 1 pair 1 000 feet max Plenum Belden 82761 22 AWG 1 pair 1 000 feet max RS 485 PVC Belden 9744 22 AWG ...

Page 16: ...ANUAL FDW1000 EXP101 TECH SUPPORT 1 888 678 9427 44 0 203 630 1653 Typical wiring diagrams The following diagrams show some typical wiring examples For simplicity each diagram shows only the connections that are relavent to the diagram s purpose Wiring common grounds ...

Page 17: ...INS_FDW1000_EXP101 01 06 2020 PAGE 17 INSTALLATION AND OPERATION MANUAL FDW1000 EXP101 TECH SUPPORT 1 888 678 9427 44 0 203 630 1653 2 wire RS 485 bus wiring for EXP101 expansion modules ...

Page 18: ...INS_FDW1000_EXP101 01 06 2020 PAGE 18 INSTALLATION AND OPERATION MANUAL FDW1000 EXP101 TECH SUPPORT 1 888 678 9427 44 0 203 630 1653 Door strike follows dry contact closure one reader ...

Page 19: ...INS_FDW1000_EXP101 01 06 2020 PAGE 19 INSTALLATION AND OPERATION MANUAL FDW1000 EXP101 TECH SUPPORT 1 888 678 9427 44 0 203 630 1653 Door strike follows LED one reader ...

Page 20: ...INS_FDW1000_EXP101 01 06 2020 PAGE 20 INSTALLATION AND OPERATION MANUAL FDW1000 EXP101 TECH SUPPORT 1 888 678 9427 44 0 203 630 1653 Door strike follows dry contact closure two readers ...

Page 21: ...INS_FDW1000_EXP101 01 06 2020 PAGE 21 INSTALLATION AND OPERATION MANUAL FDW1000 EXP101 TECH SUPPORT 1 888 678 9427 44 0 203 630 1653 Door strike follows LED two readers ...

Page 22: ... Remote pair of FDW1000s and the pair s of EXP101s have been successfully initialized and programmed A STATUS LED flashing green slowly indicates that there is no optical link between the FDW1000s A solid red STATUS indicator LED indicates that the unit is properly powered but there is no 2 wire RS 485 link A rapidly flashing green STATUS LED indicates that there is communication between the Centr...

Page 23: ...INS_FDW1000_EXP101 01 06 2020 PAGE 23 INSTALLATION AND OPERATION MANUAL FDW1000 EXP101 TECH SUPPORT 1 888 678 9427 44 0 203 630 1653 Dimensions ...

Page 24: ...INS_FDW1000_EXP101 01 06 2020 PAGE 24 INSTALLATION AND OPERATION MANUAL FDW1000 EXP101 TECH SUPPORT 1 888 678 9427 44 0 203 630 1653 AutoCAD drawings ...

Page 25: ...robed Rising MR5 1 0 0 Strobed Rising Dorado 644 1 0 1 Strobed Rising Mag Tek 1 1 0 Strobed Falling 1 1 1 Unsupervised F 2F FDW Initialization DIP switches 1 2 and 5 are not used in programming mode DIP Switches 6 7 and 8 set the number of expansion module pairs DIP Switch 3 sets the FDW to Central or Remote mode FDW Programming DIP Switch 4 sets the Relay Channel 3 function Central Remote Select ...

Page 26: ... Switches 6 7 and 8 set the polling address Polling Address Select 6 7 8 0 0 0 not used 0 0 1 Address 1 0 1 0 Address 2 0 1 1 Address 3 1 0 0 Address 4 1 0 1 Address 5 1 1 0 Address 6 1 1 1 Address 7 Data Interface Select 3 4 5 0 0 0 not used 0 0 1 Wiegand 0 1 0 Wiegand No Filter 0 1 1 Strobed Rising MR5 1 0 0 Strobed Rising Dorado 644 1 0 1 Strobed Rising Mag Tek 1 1 0 Strobed Falling 1 1 1 Unsup...

Page 27: ...203 796 5300 F 203 796 5303 TECH SUPPORT 1 888 678 9427 INFO COMNET NET SUITE 4 2 TURNBERRY PARK ROAD GILDERSOME MORLEY LEEDS UK LS27 7LE T 44 0 203 630 1652 F 44 0 113 253 7462 INFO EUROPE COMNET NET ComNet Customer Service Customer Care is ComNet Technology s global service center where our professional staff is ready to answer your questions at any time Email ComNet Global Service Center custom...