PRT-CTRL-SE
Protege SE Integrated System Controller
Installation Manual | June 2017
49
Refer to the section
Ademco 685
in the ArmorIP Internet Monitoring Application User's Manual
(227-5500-000).
For UL and ULC installations the Central Station Receiving software must have the Contact ID details as
specified, programmed for the Compromise Attempt event.
Telephone Lightning Surge Protector
Telephone lightning surge protector manufactured by L-com Inc (Model HGLN-D1-DT) shall be connected
inline to the telephone dialer T1i and R1i. Refer to the PRT-CTRL-SE wiring diagram (see page 9) of this
manual.
Hardwire Transformer Marcus M4758CT
When installed with the power supply manufactured by Marcus, Model M4758CT:
The Digital Security Controls (DSC) Model ULC-LA power indicator light assembly (Installation
Instruction No. 29001877 R0) must be installed within a conduit knockout of either the ICT Model
CAB-LARGE-UL or Bosch Model D8108A enclosure in order to provide green AC power on indication.
The Littelfuse Part No. 150322 fuseholder and Littelfuse Part No. 0312005 5A, 3AG fast-acting fuse
must be installed in-line to the Models PRT-CTRL-SE, PRT-ZX16-PCB, and PRT-RDI2-PCB.
CAN/ULC-S319-05
The Models PRT-CTRL-SE and PRT-RDI2-PCB are intended to be mounted within the Model
CAB-LARGE-UL enclosure, installed inside the protected premise, and are CAN/ULC-S319 Listed for Class
I applications only
Exit devices and wiring must be installed within the protected area.
System must be installed with at least one PRX-NPROX proximity card reader. For CAN/ULC-S319 Listed
installations, the PRX-NPROX is the only reader that may be used.
For the Models PRT-CTRL-SE and PRT-RDI2-PCB, all RS485 and reader terminal connections must be
made using shielded, grounded cable.
The Model PRX-NPROX must be connected with shielded, grounded cable.
Fail secure locking mechanism shall only be installed where allowed by the local authority having jurisdiction
(AHJ) and shall not impair the operation of panic hardware and emergency egress.
If fire resistance is required for door assembly, portal locking device(s) must be evaluated to ULC-S533 and
CAN/ULC-S104.
Must be installed with CAN/ULC-S319 Listed portal locking device(s) for ULC installations.
When installed with the power supply manufactured by Marcus, Model M4758CT:
The Digital Security Controls (DSC) Model ULC-LA power indicator light assembly (Installation
Instruction No. 29001877 R0) must be installed within a conduit knockout of either the ICT Model
CAB-LARGE-UL or Bosch Model D8108A enclosure in order to provide green AC power on indication.
The Littelfuse Part No. 150322 fuseholder and Littelfuse Part No. 0312005 5A, 3AG fast-acting fuse
must be installed in-line to the Models PRT-CTRL-SE, PRT-ZX16-PCB, and PRT-RDI2-PCB.
CAN/ULC-S559-04
Signal Reporting
Any fault of an active communication system shall be annunciated and recorded at the signal receiving
center within 180 s of the occurrence of the fault.
The Report IP and Contact ID services must be programmed and enabled within the Protege System. The
following options are required:
The Contact ID Reporting Service must be enabled and the Service Mode must be configured to start
with the operating system.
Refer to the section
Contact ID Reporting Service
in the Protege System Controller Reference Manual
(227-4045-500)
The Report IP Service must be enabled as the primary communication channel, the Service Mode
must be configured to start with the operating system, and the Reporting Protocol must be set to
ArmorIP.