Each zone input can use a different input configuration. To program a large number of zones with a certain
configuration use the multiple selection feature in the Protege System Management Suite application.
When using the No Resistor configuration, the Controller only monitors the opened and closed state of the
connected input device generating the alarm and seal conditions.
+A
UX
-
Z1
COM
CO
M
Z2
Z3
Z4
N.C Zone Contact
No EOL Resistor Zone Configuration
6.2
Resistor Value Options
When using the EOL resistor configuration, the EOL resistor option must be configured based on the site
requirements. Note that not all resistor options are supported on all Protege field modules. (Refer to Zones
Section in the Protege Reference Manual).
Value 1
Value 2
Monitored Status
1K
-
Open, Closed
<5K7
-
Open, Closed
No Resistors
-
Open, Closed
1K
1K
Open, Closed, Tamper, Short
6K8
2K2
Open, Closed, Tamper, Short
10K
10K
Open, Closed, Tamper, Short
2K2
2K2
Open, Closed, Tamper, Short
4K7
2K2
Open, Closed, Tamper, Short
4K7
4K7
Open, Closed, Tamper, Short