42
PRT-CTRL-SE
Protege SE Integrated System Controller
Installation Manual | June 2017
Validation
In order to comply with UL294 4 hr standby requirements, is the Total
Output Current less or equal to 2A?
Yes, it is 1.28A (1280mA)
Is the DC Output current (AUX2) less or equal to 1.0A (1000mA)?
Yes, it is 240mA
Is B1 current output less or equal to 1.1A (1100mA)?
Yes, it is 520mA
Is B2 current output less or equal to 1.1A (1100mA)?
Yes, it is 520mA
Is the total combined current less or equal to 2.5A (2500mA)?
Yes, it is 2.1A (2100mA)