20
PRT-RDE2-PCB
Protege Ethernet 2 Reader Expander
Installation Manual | June 2017
4
Door Access Control
The Reader Expander allows the control of two separate access controlled doors used for entry or exit only, and
a single access controlled door using entry/exit.
4.1
Reader Connection
The Protege Reader Expander allows the connection of 2 reading devices or 4 Wiegand reading devices and
the ability to control 2 doors (Entry or Exit Only) or 1 door (Entry and Exit). The following diagram shows the
connection of standard Wiegand Reader with the Protege Reader Expander controlling an Access Door and
Entry/Exit Door.
+A
UX
-
DO
L2
D1
L1
BZ
S
hield i
s
frame
grounded at
one point
S
hielded Cable
RED
BLACK
G
REEN
WHITE
ORAN
G
E
BROWN
BLUE
YELLOW
S
HIELD
S
hield not
connected
Standard Card Reader Connection
The card reader must be connected to the Controller port using a shielded cable. Always refer to the card
reader manufacturer for detailed installation guidelines. The shield connection must only be connected at one
end of the cable in the metallic enclosure(frame grounded). The beeper output on the Controller provides
diagnostic information to the end user and installer when access is denied or the unit is operating offline.
Warning:
Do not connect the shield to a AUX- or 0V connection.
Do not join the shield and black wires at the reading device.
Do not connect the shield to any shield used for isolated communication.
UL
ULC
Compatible access control card reader communication formats are: 26-, 34-, 37-Bit Wiegand,
RS-232, RS-485, and Smart RS-485.