Innovative Circuit Technology Ltd.
8
Energise each bus by closing the main external breaker or disconnect device on the
bus input lines. Check that the Distribution Panel LCD display powers up, the
internal channel relays close after a short delay, and the connected loads are
energised.
Figure 3: Front Panel
LCD Display
At power up the LCD will be displaying the Bus A main screen showing the voltage
of that bus, and total current through the bus. Press the
Bus A
Output Select
button to cycle through the Network status page, the channel output screens for
that bus, (showing on/off status, voltage, and current for each output channel on
the bus selected) and the five Site Alarm input status screens (if alarm inputs are
enabled).
Pressing the
Bus B Output Select
button will switch the display to the Bus B home
screen. Press the button to cycle through the Network status page, each channel
output screen for that bus, and the five Site Alarm input status screens (if the
alarm inputs are enabled).
Holding either
Output Select
button for two seconds will return the display to the
main screen for that bus. Holding either
Output Select
button for 20 seconds will
reset the password to the factory default (see
Password Reset
section).
The LCD backlight will activate when pressing either Output Select button, and will
turn off after approximately 15 minutes of inactivity.
The LCD menu screens display the data as described below, in the sequence shown
in Figure 4, LCD Display Screens.
LCD Output
select buttons
Bus B Output 1-10
fuses
LCD Display
Bus A Output 1-10
fuses