Innovative Circuit Technology Ltd.
17
Over-Current Threshold
: Enter the maximum total current level for the bus.
Current exceeding this level will trigger the Over-Current alarm.
Activate Form-C Contact
: Checking this box will cause the Alarm relay to
trigger for an over-current condition. (default)
Send E-mail
: Checking this box will cause the unit to send a Bus Over-Current
alarm e-mail to the assigned address entered on the
E-mail Setup
page
Output Setup
Use this page to configure the settings for each output channel on Bus A and Bus B.
Select the output to be edited in the
Select an Output to Edit
box. Make any
required changes, and then click on the
Save Settings
button at the bottom of the
page to save any edits. Click on the
Copy Settings to All
button, to copy the
settings of the selected output to all other outputs on both buses.
Output Settings:
Output Label
: Enter a descriptive label for the selected output channel if
desired.
Output State After Panel Reset
: Sets the state for the output after an input
power failure, or soft reset of the panel. Select one of the following:
•
Restore last State
: Will return the output contactor to the state
prior to the reset event (default)
•
Enable Output
: Will enable the output contactor, regardless of its
previous state
•
Disable Output
: Will disable the output contactor, regardless of its
previous state
Ignore Fuse Status:
If this box is checked, the panel will not monitor the status
of the fuse for the selected output.
Enable Power Cycling:
Check this box to enable output power cycling for the
selected output, so that the output will automatically be re-enabled after the
Sequence/Cycle Delay
time whenever the output is disabled using the
Output
Off
button on the
Status and Control
page, or when the
Network Watchdog
is
triggered. This feature is useful for remotely resetting power to hardware
required for the network connectivity of the panel.
The
Sequence/Cycle Delay
time must be set on the
Device Setup
page with
duration long enough for the connected network hardware to fully reset for
this function to be effective. Multiple outputs that are disabled using Power
Cycling will be re-enabled in sequence.