Distribution Series 3  

Dual Bus DC Load Distribution Panels  

 

INSTRUCTION MANUAL 

855-351-000 

 

Model ICT200DF-20BRC 

10/10 Intelligent GMT Fuse Panel 

Summary of Contents for Distribution 3 Series

Page 1: ...ive Circuit Technology Ltd 1 Innovative Circuit Technology Ltd Distribution Series 3 Dual Bus DC Load Distribution Panels INSTRUCTION MANUAL 855 351 000 Model ICT200DF 20BRC 10 10 Intelligent GMT Fuse...

Page 2: ...ed the 100 amperes rated capacity of each power bus Ensure load current through each output channel does not exceed 20 amperes Do not block air inlet or outlet openings in the panel sides Remove all f...

Page 3: ...11 TCP IP WEB BASED UTILITY 11 Status and Control 13 Device Setup 14 Bus Setup 16 Output Setup 17 Network setup 19 E mail Setup 22 Alarm setup 23 User Setup 24 Maintenance 24 MOBILE WEB APP 25 PASSWO...

Page 4: ...displays all panel information allows full access to channel configuration settings provides remote channel on off control and can be set up to send an alarm to user defined email accounts in the eve...

Page 5: ...ted capacity of each power bus Channel output fuses must not exceed 20 amperes maximum rating 16 amperes continuous Do not block air inlet or outlet openings in the panel sides Figure 1 Back Panel Con...

Page 6: ...required The unit may be operated with either Bus A or Bus B powered or both NOTE All channel RTN lines and the main high power Bus A and Bus B RTN terminals are common and tied to a single internal...

Page 7: ...network connected units The external sensor contacts must be voltage free as a small sense current is supplied from the panel Alarm Input pins to detect the external contact open or closed state Refer...

Page 8: ...t status screens if alarm inputs are enabled Pressing the Bus B Output Select button will switch the display to the Bus B home screen Press the button to cycle through the Network status page each cha...

Page 9: ...e of load User configurable default is channel number only Line 2 Channel output status ENABLED DISABLED to indicate internal relay state or FUSE OPEN if the fuse for the channel has tripped Line 3 Ou...

Page 10: ...Innovative Circuit Technology Ltd 10 Figure 4 LCD Display Screens...

Page 11: ...m e mail to multiple user set e mail addresses for any of the alarm conditions by enabling the e mail function on each alarm setup page on the web based interface No alarm e mails will be sent if the...

Page 12: ...ine three on the unit s front panel LCD display see Fig 4 Otherwise the panel will use the factory default IP address of 192 168 0 180 as shown above 3 Enter a username and password The default Admini...

Page 13: ...screen push buttons The status of any of the five Input Alarms for alarms that have been enabled see Alarm Setup page will be shown in the Alarm Input box A grey Alarm Input indicator box shows that t...

Page 14: ...ded Synchronize with NTP Server Check this box to select automatic synchronization with the external server recommended NTP Server Enter the name or IP address of the NTP Server used for date and time...

Page 15: ...is function to work Power for a cycled channel will be held in the off state for the duration set by the Sequence Cycle delay time then will be turned back on Watchdog Enabled Check this box to enable...

Page 16: ...ected bus if desired Bus A B Under Voltage Alarm Under Voltage Threshold Enter the bus under voltage value Bus voltage dropping below this level will trigger a Bus Under Voltage alarm Under Voltage Re...

Page 17: ...e state for the output after an input power failure or soft reset of the panel Select one of the following Restore last State Will return the output contactor to the state prior to the reset event def...

Page 18: ...lt above the Load Shedding Threshold voltage NOTE Outputs that have been disabled on the Status and Control Page will reconnect automatically if Load Shedding Auto Recovery is enabled for that output...

Page 19: ...a static IP address to the unit uncheck this box then set the following parameters IP Address Specify a unique IP address for the unit Subnet Mask Specify the mask for the subnet the panel is located...

Page 20: ...ormation such as bus voltage and channel currents The panel can send SNMP traps to the external management software when an alarm or fault occurs The information available from the SNMP agent is descr...

Page 21: ...ad write SNMP access The default write community string is write It is recommended to change the community strings before enabling SNMP as the defaults are well known SNMPv3 Settings User Name Enter t...

Page 22: ...panel Recipient E mail Addresses Enter one or more e mail addresses that are to receive all e mail notifications from the panel Use commas to separate multiple addresses This field can also be used t...

Page 23: ...A to 10A opening and have the bus B alarm output trigger for any fuse on channel 1B to 10B opening Send E mail Check this box to cause an e mail notification to be sent when a fuse opens on any of the...

Page 24: ...it Set the access level to be appropriate for the amount of control each user requires Administrator This level has full access to the panel settings and can set up users and change passwords admin is...

Page 25: ...l Setup page Ping Diagnostics Tool Use this feature to verify connectivity of any network connected device Enter the hostname or IP address of the target device and then click the Ping button MOBILE W...

Page 26: ...the outputs select buttons once to view the Network Status screen on the LCD The factory default IP address for the panel will be displayed ROUTER CONFIGURATION Use this section to set up a Distributi...

Page 27: ...in the range of 1 to 65535 See the Network Setup section for information on assigning new network ports It is important to change the panel s HTTP port from 80 if the local network has another device...

Page 28: ...olon and the HTTP port number the panel is using e g http 209 123 10 33 8000 for a router address 209 123 10 33 port 8000 Panel Access With Router Address TEXT MESSAGE ALARM NOTIFICATIONS The panel ca...

Page 29: ...cable to connect the panel to a network Ensure the network card settings on the computer are configured for accessing the IP address of the panel To access a panel with the default IP address of 192...

Page 30: ...ecipient addresses The Send Test E mail page will show an error message if the panel is unable to send the e mail Check on the E mail Setup page and ensure the SMTP Server field is the correct address...

Page 31: ...tputs enabled Alarm Form C Contacts 1 output per bus 1A 60VDC max Alarm Sensor Inputs Five external dry contact alarm inputs configurable for NC or NO contacts Applied voltage 3 3V 0 4mA for contact c...

Page 32: ...Innovative Circuit Technology Ltd 32 Weight 9 5 lbs 4 3kg Warranty 2 years Dimensions 19 0 x 9 4 x 1 7 483mm x 236mm x 45mm Figure 5 Mechanical Dimensions...

Page 33: ...the defect is discovered A valid product serial number must be provided with the RMA claim to prove eligibility The RMA procedure is available on the ICT website at www ict power com support warranty...

Page 34: ...nce or causes external to the unit including but not limited to general environmental conditions such as rust corrosive atmospheres sustained temperatures outside the specified operating range of the...