WARNING
Risk of serious personal injury or damage to equipment and property! Always observe the
following:
4
Use an appropriately rated over-current protection device in line with the main battery connection
to the Distribution Panel input to protect the high current input wiring
4
Use an appropriately rated disconnect switch or circuit breaker in line with the Distribution Panel
input to enable installation and service with the battery or power source disconnected
4
Always disconnect main power source before installing or removing fuses, or connecting or
disconnecting wiring
4
Use wire and connectors rated for the maximum load current and size of fuse or circuit breaker
4
Carefully observe wiring polarity when making input and output connections
4
Securely tighten all connections and insert fuses fully
4
No internal user serviceable parts. Refer all product service to an authorized ICT Ltd. service
facility
CAUTION
Risk of personal injury or damage to equipment! Always observe the following:
4
Fuses may be HOT to touch. Disconnect power and allow to cool before removing or replacing
4
Wiring terminals may be HOT to touch. Disconnect power and allow to cool before disconnecting
load wires
4
Install in a protected environment, keep sources of moisture away from unit
2
NOTE
Due to the breaker/fuse detection circuitry internal to the distribution panel, it may be possible to
measure a voltage on the output terminal(s) even if that output’s breaker or fuse is open (with no
load connected). This is normal operation. The detection circuitry is a high-impedance circuit,
and while a voltage may be present on the output terminal, it is purely a signal voltage and does
not support loading. Any load device connected to the output will immediately pull this voltage
to zero volts.