OPERATING AND MAINTENANCE MANUAL
Chapter 7 - Electronic controller
iC 215 ÷ iC 780
54
The data in this manual are not binding and they can be modified by the manufacturer without notice.
Reproduction of this manual is strictly prohibited
ENGLISH
EN
7 . 2 2 . 2
P a r a m e t e r s s e t t i n g
The following table shows the setting of controller parameters on the basis of the various configurations established for the
entire range of units.
Certain functions may not be active or available on all models (hence the associated parameters may not be visible on the
controller).
If the parameter is not present in the “Value” column, refer to the options listed on the right hand side of the table.
(*)
Parameter visible only on dual frequency version.
(*)
Parameter visible only on dual frequency version.
iC 215÷220
Parameter
Value
UM
Level
Freeze
protection
No
Yes
ST01
7.0
°C
U
ST02
5.0
°C
U
ST07
2.0
°C
U
CF54
See Ch.
7.22.3
--
U
CF63 (*)
0
--
U
CF64
1
--
U
Sd01
0.0
°C
U
Sd03
4.0
°C
U
Sd05
30.0
°C
U
CO19
4
10 Hours
U
AL26
4.0
°C
U
iC 303÷416
Parameter
Valu
e
UM
Level
Freeze
protection
Fans control
No
Yes
ON/OFF
Step
(i
C 408
-41
6)
Phas
e chop
ping
control
Electronic
control
ST01
7.0
°C
U
ST02
5.0
°C
U
ST07
2.0
°C
U
CF54
See Ch.
7.22.3
--
U
CF63(*)
0
--
U
CF64
1
--
U
Sd01
0.0
°C
U
Sd03
4.0
°C
U
Sd05
30.0
°C
U
CO19
4
10 Hours
U
AL26
4.0
°C
U