OPERATING AND MAINTENANCE MANUAL
Chapter 3 - Technical data
iC 215 ÷ iC 780
16
The data in this manual are not binding and they can be modified by the manufacturer without notice.
Reproduction of this manual is strictly prohibited
ENGLISH
EN
Dual frequency version (50Hz/60Hz)
:
NOTE
The values in the table may vary in relation to the unit model and configuration. In this case refer to the offer data.
NOTE
The pressure head is the pressure head available in the user’s premises. The installed pump my differ with respect to the
standard pump. For the flow rate and pressure head values two numbers are specified: the first refers to nominal conditions
and the second refers to maximum conditions.
Model
iC 660
iC 770
iC 780
Tank
capacity
water volume
(litres)
500
678
678
Pump P3
water flow rate
(m
3
/h)
9.4/48
12.5/56
14.9/56
pump pressure
head
(bar)
3.8/1.5
3.3/2.5
3.3/2.5
rated power
(kW)
4
5.5
5.5
Pump P5
water flow rate
(m
3
/h)
9.4/48
12.5/72
14.9/72
pump pressure
head
(bar)
5.5/3.1
4.8/3.4
4.8/3.4
rated power
(kW)
7.5
9.2
9.2
Axial flow
fan
No. of fans
2
3
3
total airflow
(m
3
/h)
42800
63900
62100
High
pressure
axial flow
fan
No. of fans
2
3
3
residual
pressure
(Pa)
172
191
176
total airflow
(m
3
/h)
40000
60000
60000
Model
iC 215
iC 220
iC 303
iC 305
iC 408
iC 410
iC 412
iC 416
Tank
capacity
water volume
(litres)
60
60
115
115
140
255
255
255
Pump P3
water flow rate
(m
3
/h)
0.4/4.8
0.4/4.8
0.4/4.8
0.4/4.8
2.3/9.0
2.3/9.0
3.5/16.2 3.5/16.2
50 Hz pump
pressure head
(bar)
3.1/2.0
3.1/2.0
3.1/2.0
3.1/2.0
3.1/1.9
3.1/1.9
2.4/2.0
2.4/2.0
60 Hz pump
pressure head
(bar)
4.5/3.4
4.5/3.4
4.5/3.4
4.5/3.4
4.5/3.2
4.5/3.2
3.5/3.1
3.5/3.1
rated power
(kW)
1.1
1.1
1.1
1.1
2.2
2.2
2.2
2.2
Axial flow
fan
No. of fans
1
1
1
1
1
2
2
2
total airflow
(50 Hz)
(m
3
/h)
3500
3150
6500
6150
8150
14200
13600
13600
total airflow
(60 Hz)
(m
3
/h)
4750
4200
7700
6100
9900
16900
16000
16000