Dual frequency version (50Hz/60Hz)
:
* at distance of 1 m
** global
Test conditions
Noise levels refer to operation of the unit at full load in nominal conditions.
Sound pressure level in hemispherical irradiation conditions at a distance of 1 m from the condensers side of the unit and
height of 1.6 m from the ground. Values with tolerance of ± 2 dB.
Sound pressure level:
according to ISO 3744.
50Hz
60Hz
Fan
Lp dB(A) *
Lw dB(A) **
Lp dB(A) *
Lw dB(A) **
iC 215
axial
67.4
80.4
69.5
82.5
iC 220
axial
67.4
80.4
68.9
81.9
iC 303
axial
68.1
81.1
69.6
82.6
iC 305
axial
68.1
81.1
70.7
83.7
iC 408
axial
68.6
81.6
70.9
83.9
iC 410
axial
69.1
82.1
72.2
85.0
iC 412
axial
69.1
82.1
71.2
84.2
iC 416
axial
70.0
83
72.1
85.1