background image

 

 

Without barometric damper 

 
Due to the lack of dilution air that would ordinarily be drawn into the 
barometric damper, the dew point of the flue gases is raised. To offset 
the increased tendency for vent condensation, the chimney must be 
lined. The liner must be insulated according to the insulating 
procedure recommended by the manufacturer of the liner. Also, the 
vent connector should be as short as possible and either be of double 
wall construction or of single wall construction with 25.4 mm (1") of 
insulation. 
 
 

WARNING 

 

Poisonous carbon monoxide gas hazard. 
 
Never install a hand operated damper in the vent 
pipe. However, any Underwriters Laboratories listed 
electrically operated automatic type vent damper 
may be installed if desired. Be sure to follow 
instructions provided with vent damper. Read and 
follow all instructions in this section. 
 
Failure to properly vent this furnace or other 
appliances can result in personal injury and/or 
death, property damage.

 

 
 

CAUTION 

When the furnace (chimney installation) is vented 
together with other combustion appliances such as a 
water heater, the allowable venting materials (L-Vent, 
etc.) for use with those appliances must be investigated. 

 
 

Flue pipe sizing 
 

The following table is an excerpt from the Installation Code and 
indicates the permitted flue sizes and minimum base temperatures for 
circular flues in chimneys with thermal resistance of less than R6 (6 ft

2

 

hr 

•°

F / Btu). Where a new appliance, burner, or chimney is installed, 

chimney vent sizes and maximum flue gas temperatures (measured at 
the chimney connector with the barometric damper shut, after 5 
minutes of operation) shall comply with Table 2. 
 
 

Note

: Thermal resistance values for typical chimneys 

are as follows: 

R2 (2 ft

2

 

hr 

•°

F / Btu): 

Clay-lined masonry, A-vent 

R3 (3 ft

2

 

hr 

•°

F / Btu): 

Metal liner in clay-lined Masonry 

R6 (6 ft

2

 

hr 

•°

F / Btu):   Metal or clay-lined masonry with R4.5 (4.5 

ft

2

 

 hr 

•°

F / Btu) insulation between liner 

and masonry (e.g. 2" of expanded mica or 1 
3/8" of high density glass fibreboard.) 

 
 

Applying Table 2 
 

If a furnace with a 0.60 USGPH nozzle is to be connected to a 20 foot 
tall clay-lined masonry chimney, the thermal resistance of this type of 
chimney is R2, (which is less than R6). The actual firing rate at 156 
psig is 1.25 x .60 = .75. Therefore this table shall apply as follows:  

The minimum size permitted shall be 101.6 mm (4") inside diameter; 

The maximum size permitted shall be 127.0 mm (5") inside diameter; 

The minimum base temperature shall be about 160

°

C (320

°

F). 

 
 

1.4.3)  Side-wall venting - DV-2000™ 

Direct Vent System 

 

The furnace can be side-wall vented without the use of a side-wall 
power vent, using the new DV-2000™ venting system with the high 
static pressure Beckett AFII and Riello 40-BF oil burners. 

Outdoor 

combustion air must be directly connected to the burner or the 
DV-2000™ venting system will not function.  
 

The notable characteristics of the DV-2000™ system are as follows: 

a) 

Certified to use the following materials for ducting the intake air 
from the terminal to the burner: Schedule 40 PVC DWV, 
Schedule 40 ABS DWV, and ASTM 2729 sewer Pipe; 

b) 

One hole of minimal size (152.4 mm

ø

 / 6"

ø

) is required to be cut 

into the side-wall, and the terminal is designed to fit through a 
minimum 2 X 8 joist space;

 

c) 

Incorporates a vent blockage safety shutdown system. If the vent 
or intake opening ever becomes partially or fully blocked, the 
burner will shut down before a #1 smoke condition occurs;

 

d) 

The intake and vent circuits within the terminal can be accessed 
for cleaning. 

 

There are 3 main components to the DV-2000™ system: the VTK vent 
terminal kit, the IFV insulated flexible venting material and the 
field-supplied 3 inch PVC or ABS intake piping. 
 
 
 
 
 
 

 
 
 
 
 

TABLE 2 

 

Total input rating of all 

connected appliances 

Flue inside diameter 

Minimum base temperature 

for chimney height of: 

kW 

Btu/h 

USGPH 

Min. 

Max. 

11' 

20' 

28' 

36' 

21 70,000 0.50 

76.2 mm (3") 

0.13 m (5") 

149°C / 300°F 

204°C / 400°F 

279°C / 535°F 

385°C / 725°F 

27 91,000 0.65 

76.2 mm (3") 

0.13 m (5") 

135°C / 275°F 

171°C /  340°F 

221°C / 430°F 

279°C / 535°F 

31 105,000 0.75 

0.1 m (4") 

0.13 m (5") 

127°C / 260°F 

160°C  / 320°F 

193°C / 380°F 

246°C / 475°F 

36 119,000 0.85 

0.1 m (4") 

0.13 m (5") 

121°C / 250°F 

149°C  / 300°F 

179°C / 355°F 

221°C / 430°F 

41 140,000 1.00 

0.1 m (4") 

0.15 m (6") 

107°C / 225°F 

149°C  / 300°F 

185°C / 365°F 

221°C / 430°F 

51 175,000 1.25 

0.1 m (4") 

0.15 m (6") 

116°C / 240°F 

135°C  / 275°F 

160°C / 320°F 

185°C / 365°F 

 

445 01 4024 05

Summary of Contents for OCF105A12C

Page 1: ...CING OF THE UNIT AND KEEP THE DOCUMENT NEAR THE FURNACE FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE Printed in Canada Printed on 100 recycled paper OIL...

Page 2: ...s and test instruments Failure to carefully read and follow all instructions in this manual can result in personal injury and or death property damage furnace malfunction WARNING Fire hazard The furna...

Page 3: ...ions regarding any brand or type of detector CAUTION Ensure that the area around the combustion air intake terminal is free of snow ice and debris CAUTION An air pressure switch MUST be used when the...

Page 4: ...ine or any other damaging chemicals Refer to Part 1 section 5 2 1 4 VENTING 1 4 1 General The furnaces can be vented in several ways Chimney Vented Using the Beckett AFG or Riello 40 F burner the furn...

Page 5: ...ected to a 20 foot tall clay lined masonry chimney the thermal resistance of this type of chimney is R2 which is less than R6 The actual firing rate at 156 psig is 1 25 x 60 75 Therefore this table sh...

Page 6: ...nal in accordance with all local and national codes The following requirements shall be considered to be minimum requirements that can be overridden by stricter local and national codes FIGURE 1 The v...

Page 7: ...hat the band will close with an action of one strip sliding over the other not under the gear head of the draw clamp see Figure 1 8 Tighten the band clamp with considerable torque to cause the gum sea...

Page 8: ...E BACK 5 THREAD SPIN SLEEVE BACK 10 CUT STAINLESS STEEL CORE BACK BY 3 9 FIGURE 1 3 FIGURE 1 4 FIGURE 1 1 FIGURE 1 2 FIGURE 1 5 FIGURE 1 6 INSERT STAINLESS STEEL CORE ONTO BREECH TUBE DRIVE THREE STAI...

Page 9: ...IGURE 1 8 SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT TERMINAL SEALANT OUTFLOW FIGURE 1 11 10 APPLY THE SEALANT TO THE TUBE END SEALANT OUTFLOW SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT BREECH TWI...

Page 10: ...TIGHTLY INTO RECESS INSTALL STABILIZER SHROUD CAULK TO SEAL STABILIZER SHROUD TO THE WALL FIGURE 1 13 FIGURE 1 14 FIGURE 1 12 VENT TERMINAL PRESSURE SWITCH REFER TO WIRING DIAGRAM FOR ELECTRICAL CONNE...

Page 11: ...t 1 section 5 3 1 5 3 Outdoor Combustion Air Side wall Venting DV 2000 for a complete description 1 5 AIR FOR COMBUSTION WARNING Poisonous carbon monoxide gas hazard Comply with NFPA standards for the...

Page 12: ...two plastics Intake pipe length DV 2000 The DV 2000 venting system has been certified for 37 equivalent m 120 equivalent feet of 3 intake pipe Count a 90 elbow as 10 equivalent feet and a 45 elbow as...

Page 13: ...king Checking the air and turbulator settings Before starting the burner for the first time adjust the air and turbulator settings to those listed in Table 4 Once the burner becomes operational final...

Page 14: ...e heat exchanger Wire the thermostat and condensing unit contactor as indicated in the wiring diagram Figure 6 1 9 4 Ductwork and Filter Installation Design and install the air distribution system to...

Page 15: ...Fan Limit Control heats up to the factory set point the circulating air blower starts 7 The circulating air blower and burner motor remain on until the thermostat is satisfied Also the solenoid valve...

Page 16: ...shut down for an extended period of time 4 Set thermostat higher than the room temperature 5 If the burner motor does not start or ignition fails turn off the disconnect switch and CALL A QUALIFIED SE...

Page 17: ...flame should shut down before a 1 smoke reading occurs 3 Gradually block the vent outlet The burner flame should shut down before a 1 smoke reading occurs 4 If the burner does not shut down before 1...

Page 18: ...ly from the front inspection port Also the furnace has external clean out ports so the soot does not fall into the fan compartment during the cleaning operation IMPORTANT Do not vacuum the ceramic cha...

Page 19: ...een installed the burner will have to be removed to check the retention head 3 1 4 Nozzle Replace the nozzle with the one specified in Table 4 3 1 5 Oil filters Tank filter The tank filter should be r...

Page 20: ...hone Day Night Dealer name and address START UP TEST RESULTS Nozzle Pressure lbpsi Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Ambient t...

Page 21: ...3 3 4 5 AFUE From CSA B212 standard and Canadian regulation 81 5 81 0 80 3 AFUE From ASHRAE 103 standard and US regulation 81 5 81 0 80 3 RIELLO BURNER SIDE WALL INSTALLATION Burner tube insertion len...

Page 22: ...DNS 0589 Rev C FIGURE 5 Models ODH53F100LB 3MC OCF105A12C 23 445 01 4024 05...

Page 23: ...24 FIGURE 6 Wiring diagram ODH53F100LB 3MC OCF105A12C 445 01 4024 05...

Page 24: ...COMPONENTS AND REPLACEMENT PARTS 25 445 01 4024 05...

Page 25: ...PARTS LIST Model ODH53F100LB 3MC OCF105A12C B50030A 26 445 01 4024 05...

Page 26: ...gonal nut 3 8 16NC brass F07F024 32 Washer panel peep hole B30752 33 Hexagonal flange nut 3 8 16NC brass F07O001 34A 5 breech plate B30459 34B 3 breech plate B30515 35 Gasket breech plate B30415 02 36...

Reviews: