background image

 

 

 

6. 

Pry the bottom half of the heat exchanger apart by using the 
designated prying tabs; 

7. 

Remove the bottom half of the heat exchanger through the front 
of the furnace; 

8.  Pull the firepot up and out of the bottom half of the heat 

exchanger; 

9. 

Remove the old sealing gasket from the flange of the upper half 
of the heat exchanger; 

10.  Scrape any residual gasket material off the matching flanges of 

the heat exchanger. 

 

Replacing the firepot 

 

1. 

Align the slot at the front part of the firepot with the burner tube 
sleeve and gently lower the firepot into the bottom half of the heat 
exchanger; 

2. 

Holding the firepot near the perimeter, gently push the firepot all 
the way into the bottom half of the heat exchanger until it is 
properly seated; 

3. 

Thoroughly wet the gasket with water using a spray pump bottle, 
position the tabs over the studs, and push the gasket upward 
against the sealing flange of the upper half of the heat 
exchanger; 

4.  Install the brass nuts on the studs by engaging only 2 or 3 

threads; 

5. 

Position the bottom half of the heat exchanger underneath the 
upper half and align the bottom half so that the slots in the bolting 
tabs engage the stainless steel studs. There is no further need to 
hold onto the bottom half as it will now be suspended on the stud 
nuts; 

6. 

Push upward on the housing and thread the nuts finger-tight as 
far as possible; 

7. 

Intermittently tighten the brass nuts with a wrench in a sequence 
that will pull the heat exchanger halves together evenly. Tighten 
all nuts to 90 inch-lbs torque once and then alternately re-tighten 
all nuts again to 100 inch-lb. 

THE RE-TIGHTENING SEQUENCE 

IS ABSOLUTELY NECESSARY TO ENSURE A TIGHT JOINT

8.  Re-assemble the front panel, breach plate, Limit Control and 

burner in reverse sequence to their removal; 

9. 

Follow the instructions for starting the burner for the first time to 
cure the firepot and perform combustion checks. See Section 
2.3. 

 

3.1.3) Drawer 

assembly 

 

Remove the drawer assembly. Clean all foreign matter from the 
retention head and electrodes. If a Beckett AFG burner has been 
installed, the burner will have to be removed to check the retention 
head.  
 

3.1.4) Nozzle 

 
Replace the nozzle with the one specified in Table 4. 
 

3.1.5) Oil 

filters 

 

Tank filter 

The tank filter should be replaced as required.  
 

Secondary filter 

The 10 (or less) micron filter cartridges should be replaced annually. 

 

3.1.6) Air 

filters 

 
Air filters are the disposable type. They should be replaced at least 
once a year. Dusty conditions, presence of animal hair etc. may 
require much more frequent filter changes. Dirty filters will impact 
furnace efficiency and increase oil consumption. 
 

3.1.7) Motor 

lubrication 

 
Do NOT lubricate the oil burner motor or the direct drive blower motor 
as they are permanently lubricated.  
 

3.1.8)  CAS-2B combustion air kit (chimney 

venting) 

 
If used, check the CAS-2B combustion air kit for proper operation. 
Check to see that the inlet screen is not plugged. Block the air inlet 
completely and ensure that a zero smoke reading results. If a zero 
smoke reading is not obtained, set up the burner as indicated in Part 
2, section 3.  
 
Gradually block off the intake. The CO

2

 should increase to a maximum 

of 0.5 percentage points at the fully blocked condition. If not, check 
that the VRV gate is pivoting freely and that the pivot rod is in a 
horizontal position. Also, check that the counterweight has been 
properly adjusted in accordance with CAS-2B installation instructions. 

 

3.1.9)  Blocked Vent Shut-Off (BVSO)

 

Cleaning 

 

For continued safe operation, the Blocked Vent Shut-Off System 
(BVSO) is required to be inspected and maintained annually by a 
qualified agency. 

1. 

Disconnect the power to the appliance. 

2. 

Remove the two screws holding on the BVSO assembly cover. 

3. 

Remove the cover. 

4.  Remove the two screws holding the thermal switch to the 

assembly base. 

6. 

Without removing the electrical wires, remove the thermal switch 
and remove any build-up from the thermal switch surface. 

 

CAUTION 

Do not dent or scratch the surface of the thermal 
switch. If the thermal switch is damaged, 
replacement is required.  

 
6. 

Clear and remove any build-up or obstruction inside the heat 
transfer tube. 

7. 

Re-mount the thermal switch to the assembly base. 

8. 

Re-attach the assembly cover with the screws removed in step 2. 

9. 

Re-establish power to the appliance. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

20 

445 01 4024 05

Summary of Contents for OCF105A12C

Page 1: ...CING OF THE UNIT AND KEEP THE DOCUMENT NEAR THE FURNACE FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE Printed in Canada Printed on 100 recycled paper OIL...

Page 2: ...s and test instruments Failure to carefully read and follow all instructions in this manual can result in personal injury and or death property damage furnace malfunction WARNING Fire hazard The furna...

Page 3: ...ions regarding any brand or type of detector CAUTION Ensure that the area around the combustion air intake terminal is free of snow ice and debris CAUTION An air pressure switch MUST be used when the...

Page 4: ...ine or any other damaging chemicals Refer to Part 1 section 5 2 1 4 VENTING 1 4 1 General The furnaces can be vented in several ways Chimney Vented Using the Beckett AFG or Riello 40 F burner the furn...

Page 5: ...ected to a 20 foot tall clay lined masonry chimney the thermal resistance of this type of chimney is R2 which is less than R6 The actual firing rate at 156 psig is 1 25 x 60 75 Therefore this table sh...

Page 6: ...nal in accordance with all local and national codes The following requirements shall be considered to be minimum requirements that can be overridden by stricter local and national codes FIGURE 1 The v...

Page 7: ...hat the band will close with an action of one strip sliding over the other not under the gear head of the draw clamp see Figure 1 8 Tighten the band clamp with considerable torque to cause the gum sea...

Page 8: ...E BACK 5 THREAD SPIN SLEEVE BACK 10 CUT STAINLESS STEEL CORE BACK BY 3 9 FIGURE 1 3 FIGURE 1 4 FIGURE 1 1 FIGURE 1 2 FIGURE 1 5 FIGURE 1 6 INSERT STAINLESS STEEL CORE ONTO BREECH TUBE DRIVE THREE STAI...

Page 9: ...IGURE 1 8 SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT TERMINAL SEALANT OUTFLOW FIGURE 1 11 10 APPLY THE SEALANT TO THE TUBE END SEALANT OUTFLOW SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT BREECH TWI...

Page 10: ...TIGHTLY INTO RECESS INSTALL STABILIZER SHROUD CAULK TO SEAL STABILIZER SHROUD TO THE WALL FIGURE 1 13 FIGURE 1 14 FIGURE 1 12 VENT TERMINAL PRESSURE SWITCH REFER TO WIRING DIAGRAM FOR ELECTRICAL CONNE...

Page 11: ...t 1 section 5 3 1 5 3 Outdoor Combustion Air Side wall Venting DV 2000 for a complete description 1 5 AIR FOR COMBUSTION WARNING Poisonous carbon monoxide gas hazard Comply with NFPA standards for the...

Page 12: ...two plastics Intake pipe length DV 2000 The DV 2000 venting system has been certified for 37 equivalent m 120 equivalent feet of 3 intake pipe Count a 90 elbow as 10 equivalent feet and a 45 elbow as...

Page 13: ...king Checking the air and turbulator settings Before starting the burner for the first time adjust the air and turbulator settings to those listed in Table 4 Once the burner becomes operational final...

Page 14: ...e heat exchanger Wire the thermostat and condensing unit contactor as indicated in the wiring diagram Figure 6 1 9 4 Ductwork and Filter Installation Design and install the air distribution system to...

Page 15: ...Fan Limit Control heats up to the factory set point the circulating air blower starts 7 The circulating air blower and burner motor remain on until the thermostat is satisfied Also the solenoid valve...

Page 16: ...shut down for an extended period of time 4 Set thermostat higher than the room temperature 5 If the burner motor does not start or ignition fails turn off the disconnect switch and CALL A QUALIFIED SE...

Page 17: ...flame should shut down before a 1 smoke reading occurs 3 Gradually block the vent outlet The burner flame should shut down before a 1 smoke reading occurs 4 If the burner does not shut down before 1...

Page 18: ...ly from the front inspection port Also the furnace has external clean out ports so the soot does not fall into the fan compartment during the cleaning operation IMPORTANT Do not vacuum the ceramic cha...

Page 19: ...een installed the burner will have to be removed to check the retention head 3 1 4 Nozzle Replace the nozzle with the one specified in Table 4 3 1 5 Oil filters Tank filter The tank filter should be r...

Page 20: ...hone Day Night Dealer name and address START UP TEST RESULTS Nozzle Pressure lbpsi Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Ambient t...

Page 21: ...3 3 4 5 AFUE From CSA B212 standard and Canadian regulation 81 5 81 0 80 3 AFUE From ASHRAE 103 standard and US regulation 81 5 81 0 80 3 RIELLO BURNER SIDE WALL INSTALLATION Burner tube insertion len...

Page 22: ...DNS 0589 Rev C FIGURE 5 Models ODH53F100LB 3MC OCF105A12C 23 445 01 4024 05...

Page 23: ...24 FIGURE 6 Wiring diagram ODH53F100LB 3MC OCF105A12C 445 01 4024 05...

Page 24: ...COMPONENTS AND REPLACEMENT PARTS 25 445 01 4024 05...

Page 25: ...PARTS LIST Model ODH53F100LB 3MC OCF105A12C B50030A 26 445 01 4024 05...

Page 26: ...gonal nut 3 8 16NC brass F07F024 32 Washer panel peep hole B30752 33 Hexagonal flange nut 3 8 16NC brass F07O001 34A 5 breech plate B30459 34B 3 breech plate B30515 35 Gasket breech plate B30415 02 36...

Reviews: