iMAT 14
32
Maintenance recommendation:
• Housing and valve should be cleaned
once a year.
• Replace wearing parts once a year.
Set of wearing parts (
x
)
iMAT 14
4020183-ICP
Functional test of iMAT 14 device:
• Briefly press test button 2 sec.
• Valve opens for condensate discharge.
Checking of alarm signal:
• Shut off condensate inflow.
• Press test button for at least 1 minute.
• Red LED flashes (after 1 minute).
• Alarm signal is being relayed.
english
Maintenance • Mantenimiento • Entretien •
Manutenção