ICP AMP105-IE2 Installation Instructions And Homeowner'S Manual Download Page 43

 

11

PART 2

 

START-UP 

 

 

2.1) OPERATIONAL 

CHECKLIST 

 

1=> 

Has the blower wheel support been removed? 

2=> 

Has the electrical wiring been completed 

according to Figures 12.1 to 12.8? 

3=> 

Has the access blower door been secured in 

place? 

4=> 

Is the valve on the oil line open? 

5=> 

Has the ‘’RESET BUTTON’’ on the Primary 

Control been pushed? 

6=> 

Is the flame observation door and the two clean-

out access doors located at the front of the unit 
closed? 

7=> 

Is the room thermostat in the heating mode and 

set above room temperature? 

8=> 

Set the main electrical switch to the ‘’ON’’ 
position and the burner should start

 
 

CAUTION 

Do not tamper with the unit or its controls. Call a 
qualified service technician. 

 
 

2.2) COMBUSTION 

CHECK

  

 
In order to obtain optimum performance from the oil burner, 
the following set-up procedures must be followed by referring 
to the Technical Specifications (Table 3) in this manual:  

1.  A test kit to measure the smoke, flue draft and over-fire 

draft should be used in order to obtain the proper air 
band setting. Although all of the above measurements 
are required for optimum set up and efficiency, the most 
important reading that must be taken is the smoke 
number in the flue pipe or at the smoke test port on the 
breech plate (SCS); 

2.  The proper smoke number, as established by way of 

engineering tests, is between 0 and 1. This degree of 
smoke emission is commonly referred to as a “trace”. It 
is recommended that a Bacharach True Spot Smoke 
Test kit or equivalent be used; 

3.  On chimney installations only, a barometric draft 

regulator (supplied with the furnace) must be installed as 
closely to the breech of the furnace as possible, in order 
to ensure proper draft through the furnace. The 
barometric damper must be mounted with the hinge pins 
in a horizontal position and the face of the damper 
vertical for proper functioning, (see instructions included 
with damper). After the furnace has been firing for at 
least five minutes, the draft regulator should be set to 
between -0.025

"

 W.C. and -0.035

"

 W.C.; 

4.  For flue pipe pressure on sidewall installations (SCS), 

refer to the Technical Specifications in this manual; 

5.  The overfire draft, which is taken through the 

observation door located in the centre of the front panel 
above the burner, is a measurement that is necessary to 
determine if there is a blockage in the heat exchanger or 
the flue pipe. Refer to the Technical Specifications in 
this manual for overfire pressure values. A high 
pressure condition may be caused by excessive 
combustion air due to the air band being too wide open 
or a lack of flue draft (chimney effect) or some other 
blockage, such as soot in the secondary section of the 
heat exchanger or the use of an oversize nozzle input or 
high pressure pump; 

6. CO

2

 and flue temperature instruments will enable you to 

obtain the data that are required to determine the true 
efficiency of the furnace. Although this information is 
nice to have, it is not essential in the basic set up of the 
furnace. The proper procedure for performing this 
operation is as follows: 

a.  Start the appliance and from the test port provided 

on the BREECH PLATE (SCS) or on the flue pipe 
just before the draft regulator (chimney application), 
proceed with the smoke test and adjust the burner 
to a setting of between a “trace” and #1 smoke after 
5 to 10 minutes of operation; 

b.  Take a CO

2

 reading and mark it down; 

c.  Open the burner air shutter to get 1.5% CO

2

 less 

than the previous reading noted in b. above and 
take a smoke test on this condition; 

d.  The new smoke reading should give you a ZERO 

smoke reading. 

7.  A 10-micron (or less) oil filter should be installed as 

closely to the burner as possible with all oil burners, but 
it is essential for burners with a low firing rate. We 
recommend the use of a low pressure drop oil filter with 
a capacity greater than that of the fuel pump; 

8.  On a new installation, the air trapped in the oil line 

leading from the tank to the nozzle must be thoroughly 
purged in order to prevent excessive after drip. The oil 
pump is equipped with a special fitting that facilitates the 
purging of any air between it and the tank. The proper 
procedure for performing this operation is as follows: 

a.  Place a piece of 1/4” dia. clear plastic tubing over 

the purge fitting on the oil pump; 

b.  Start the oil burner, then open the purge fitting and 

allow the burner to run until the purge tube is 
completely free of air bubbles; 

c. 

At this point tighten the purge fitting, which will allow 
the oil to run to the nozzle and fire the burner. If the 
purging takes longer than 15 seconds and no flame 
has been established the burner will stop. Push the 
reset button on top of the Primary Control to restart 
the burner. 

For detailed information on the operation of the Primary 
Control refer to the instructions included with the furnace 
or the burner. 

Summary of Contents for AMP105-IE2

Page 1: ...ntr les Appeler un technicien qualifi Mod les AMP105 IE2 AMP120 IE2 BMF 105 BMF 125 LBM105 LBM120 2006 03 17 X40002 Rev L INSTALLATION MULTIPOSITION AVEC CHEMIN E INSTALLATION EN D BIT ASCENDANT AVEC...

Page 2: ...ERTISSEMENT il est utilis pour indiquer les pratiques dangereuses qui peuvent provoquer des dommages corporels et ou mat riels mineurs MISE EN GARDE N utiliser qu avec du mazout 2 maximum Ne pas utili...

Page 3: ...n raccordement un vent de dimensions ad quates La capacit d air de cet appareil de chauffage central est con ue pour permettre le refroidissement du d bit d air Se r f rer au tableau 4 pour conna tre...

Page 4: ...T Ne pas obstruer les ouvertures d air de combustion de l appareil de chauffage central Toute obstruction r sultera en une combustion inad quate et accro t les risques d incendie et ou de dommages cor...

Page 5: ...ble d installer des pales acoustiques rotatives ou d isoler les conduits tel que d crit au point b d Si une seule grille d air est utilis e les conduites entre la grille et l appareil de chauffage cen...

Page 6: ...hemin e de ma onnerie Cet appareil de chauffage central peut tre vacu dans une chemin e de ma onnerie existante Toutefois l appareil de chauffage central ne doit pas tre vacu dans une chemin e vacuant...

Page 7: ...unit et le r gulateur de tirage tel qu indiqu sur les instructions fournies avec le dispositif d arr t anti refoulement Le dispositif d arr t doit aussi faire l objet d un entretien annuel R f rer au...

Page 8: ...refoulement Installation en d bit d air ascendant et vacuation verticale FIGURE4 Arrangement g n ral du syst me anti refoulement Installation en d bit d air ascendant et vacuation horizontale FIGURE...

Page 9: ...e est fix e au tube d air du br leur et aucun ajustement n est requis pour la longueur d insertion AVERTISSEMENT Si le relais de combustion install sur le br leur est de la s rie R7184 de Honeywell NE...

Page 10: ...tiliser TABLEAU 2 Fournaise Mod les Filtre air Dim Ouverture Dim AMP LBM et BMF 075 090 et 105 16 x 24 15 x 23 AMP LBM et BMF 120 140 et 155 18 x 30 17 x 29 1 3 11 Installation l horizontale ou d bit...

Page 11: ...25 W C et 035 W C 4 Pour les installations avec vacuateur mural SCS la pression dans le tuyau d vacuation doit correspondre celle sp cifi e dans les tableaux de sp cifications techniques 5 La pression...

Page 12: ...en fermant les registres de retour d air et laisser l appareil de chauffage central s teindre en limite lev e Le br leur va s teindre OFF et le ventilateur principal devrait continuer fonctionner Enle...

Page 13: ...ecyclage voir section 2 9 3 et fera 3 essais de d marrage Le nombre d essais maximum est de 3 Apr s le contr le R7184 tombe en mode s curit lockout state 2 9 2 V rification de la pression et du vacuum...

Page 14: ...appareil de chauffage central sans filtre air Les filtres jetables devraient tre remplac s au moins une fois par ann e Si l appareil de chauffage central est quip pour la climatisation les filtres dev...

Page 15: ...AVERTISSEMENT Assurez vous que le ventilateur est ad quatement soutenu quand vous le sortez des rails surtout en position horizontale ou en d bit descendant afin d viter d chapper le ventilateur et d...

Page 16: ...sse du technicien de service R SULTAT DU TEST DE MISE EN MARCHE Gicleur Pression lb po 2 Ajustements du br leur Bande principale Bande fine Position de la t te CO2 Indice de fum e Bacharach Temp ratur...

Page 17: ...BE 3 3 8 D flecteur bas r gime NON Disque statique mod le 2 3 4 3383 Gicleur 100 PSIG pression pompe Delavan 0 60 70B 0 65 70B 0 75 70B 0 85 70W 1 00 70W Pression de la pompe PSIG 120 135 130 140 120...

Page 18: ...ALE LA CONDUITEPREMIERS 6 PI 2 2 3 DESSOUS FOURNAISE PLANCHER COMBUSTIBLEAVEC BASE 0 0 0 HORIZONTALE OU SOUS LE TUYAU FUM E 4 4 4 VERTICALE AU DESSUS DU TUYAU FUM E 9 9 9 DEVANT FOURNAISE 8 8 24 C T D...

Page 19: ...ALE LA CONDUITEPREMIERS 6 PI 2 2 3 DESSOUS FOURNAISE PLANCHER COMBUSTIBLEAVEC BASE 0 0 0 HORIZONTALE OU SOUS LE TUYAU FUM E 4 4 4 VERTICALE AU DESSUS DU TUYAU FUM E 9 9 9 DEVANT FOURNAISE 8 8 24 C T D...

Page 20: ...FIGURE 12 1 Diagramme lectrique AMP LBM BMF 075 090 et 105 br leur Beckett 21...

Page 21: ...FIGURE 12 2 Diagramme lectrique AMP LBM BMF 120 140 et 155 br leur Beckett 22...

Page 22: ...FIGURE 12 3 Diagramme lectrique AMP LBM BMF 075 090 et 105 br leur Riello 23...

Page 23: ...FIGURE 12 4 Diagramme lectrique AMP LBM BMF 120 140 et 155 br leur Riello 24...

Page 24: ...FIGURE 12 5 Diagramme lectrique AMP LBM BMF 075 090 105 120 140 et 155 br leur Beckett et vacuateur SMH 25...

Page 25: ...FIGURE 12 6 Diagramme lectrique AMP LBM BMF 075 090 105 120 140 et 155 br leur Riello et vacuateur SMH 26...

Page 26: ...FIGURE 12 7 Diagramme lectrique AMP LBM BMF 075 090 et 105 br leur B SCS 27...

Page 27: ...FIGURE 12 8 Diagramme lectrique AMP LBM BMF 120 140 et 155 br leur B SCS 28...

Page 28: ...29 COMPOSANTES ET PI CES DE REMPLACEMENT...

Page 29: ...LISTE DE PI CES Code de fabrication AMP LBM BMF 075 090 105 30 B50058A...

Page 30: ...85 02 COMPREND PANNEAU ISOLATION ET DEFLECTEUR 25 ISOLATION PANNEAU DE COTE B01645 02 26 HAUTE LIMITE 195 30F R02R003 27 GARNITURE COUVERCLE DE TUYAU A FUMEE B01214 28 GARNITURE BRIDE FIXE BECKETT N04...

Page 31: ...LISTE DE PI CES Code de fabrication AMP LBM BMF 120 140 155 32 50062A...

Page 32: ...E B01875 02 COMPREND PANNEAU ISOLATION ET DEFLECTEUR 25 ISOLATION PANNEAU DE COTE B01800 02 26 HAUTE LIMITE 175 20F R02R005 27 GARNITURE COUVERCLE TUYAU DE FUMEE B00205 28 GARNITURE BRIDE FIXE BECKETT...

Page 33: ...imentation d huile B02251 7B Isolation urethane bas 3 4 x 17 B01526 80 24 Pompe avec valve soleno de N01Z068 7C Isolation urethane haut 3 4 x 22 1 2 B01526 81 25 Harnais pour bobine N01Z069 8 D tecteu...

Page 34: ...l a qualified service technician Models AMP105 IE2 AMP120 IE2 BMF 105 BMF 125 LBM105 LBM120 2006 03 17 X40002 Rev L MULTI POSITION INSTALLATIONS WITH CHIMNEY UPFLOW INSTALLATIONS WITH SEALED COMBUSTIO...

Page 35: ...esult in death or serious bodily and or material damage CAUTION Hazards or unsafe practices which CAN result in minor bodily and or material damage WARNING For use with grade 2 Fuel Oil maximum Do not...

Page 36: ...and connection to a properly sized vent The air handling capacity of this furnace is designed for cooling as well Refer to Table 4 for the expected airflow at various external static pressures 1 3 LOC...

Page 37: ...to provide combustion air requirements In unconfined spaces in buildings of conventional frame brick or stone construction infiltration may be adequate to provide air for combustion ventilation and d...

Page 38: ...ARNING The coil MUST be installed on the air discharge side of the furnace Under no circumstances should the airflow be such that cooled conditioned air is allowed to pass over the furnace heat exchan...

Page 39: ...h the furnace must be used for the proper functioning Installation instruction are included with the control 1 3 5 BLOCKED VENT SHUT OFF BVSO FOR CHIMNEY VENTING WARNING It is imperative that this dev...

Page 40: ...Blocked Vent Shut Off device wiring Installation Horizontal with vertical exhaust Blocked Vent Shut Off device wiring Installation Upflow with horizontal exhaust FIGURE 4 Blocked Vent Shut Off device...

Page 41: ...ir tube and no adjustment is required for insertion length CAUTION NEVER use the interrupted ignition function if a Honeywell R7184 series combustion relay is installed on the burner Oil Connections C...

Page 42: ...de panel or on the bottom of the furnace to accommodate the return air ductwork A sufficient clearance should be provided for air filter access Refer to Table 2 for filter rack flange dimensions for r...

Page 43: ...the heat exchanger or the flue pipe Refer to the Technical Specifications in this manual for overfire pressure values A high pressure condition may be caused by excessive combustion air due to the air...

Page 44: ...able 4 2 8 Constant Blower Switch This furnace is equipped with a constant low speed blower option Whenever the room thermostat is not calling for heating or cooling the blower will run on low speed i...

Page 45: ...er than 0 8 W C there is an obstruction in the flue pipe If the vacuum reading is close to or greater than 0 8 W C there is an obstruction in the air inlet pipe 2 9 3 R7184 Control operation Three sec...

Page 46: ...exchanger or flue pipe every year but it is advisable to have a qualified service technician check the unit before each heating season to determine whether cleaning or replacement of parts is necessar...

Page 47: ...UTION Do not dent or scratch the surface of the thermal switch If the thermal switch is damaged replacement is required 6 Clear and remove any build up or obstruction inside the heat transfer tube 7 R...

Page 48: ...y for w ire sizing Max w ire lenght ft Max fuse size Amps Control transformer External control pow er available Heating Cooling BLOWER DATA Blow er speed at 0 50 W C static pressure MED LOW MED HIGH H...

Page 49: ...RM AIR DUCT WITHIN 6 ft OF FURNACE 2 2 3 BOTTOM FURNACE COMBUSTIBLEFLOOR WITH SUB BASE 0 0 0 HORIZONTALLY OR BELOW FLUEPIPE 4 4 4 VERTICALLY ABOVEFLUEPIPE 9 9 9 FRONT FURNACE 8 8 24 SIDES TOP FLUEPIPE...

Page 50: ...M AIR DUCT WITHIN 6 ft OF FURNACE 2 2 3 BOTTOM FURNACE COMBUSTIBLEFLOOR WITH THESUB BASE 0 0 0 HORIZONTALLY OR BELOW FLUEPIPE 4 4 4 VERTICALLY ABOVEFLUEPIPE 9 9 9 FRONT FURNACE 8 8 24 SIDES TOP FLUEPI...

Page 51: ...19 FIGURE 12 1 Wiring diagram AMP LBM BMF 075 090 105 Beckett burner...

Page 52: ...20 FIGURE 12 2 Wiring diagram AMP LBM BMF 120 140 155 Beckett burner...

Page 53: ...21 FIGURE 12 3 Wiring diagram AMP LBM BMF 075 090 105 Riello burner...

Page 54: ...22 FIGURE 12 4 Wiring diagram AMP LBM BMF 120 140 155 Riello burner...

Page 55: ...23 FIGURE 12 5 Wiring diagram AMP LBM BMF 075 090 105 120 140 155 Beckett burner and sidewall venter SMH...

Page 56: ...FIGURE 12 6 Wiring diagram AMP LBM BMF 075 090 105 120 140 155 Riello burner and sidewall venter SMH 24...

Page 57: ...FIGURE 12 7 Wiring diagram AMP LBM BMF 075 090 105 B SCS burner 25...

Page 58: ...FIGURE 12 8 Wiring diagram AMP LBM BMF 120 140 155 B SCS burner 26...

Page 59: ...27 COMPONENTS AND REPLACEMENT PARTS...

Page 60: ...PARTS LIST Model AMP LBM BMF 075 090 105 28 B50058A...

Page 61: ...H BECKETT N04Z026 29A BURNER ASSEMBLY B03091 01 29B BURNER RIELLO 40 F3 N01F011 30 HEXAGONAL NUT 3 8 16NC ZINC F07F011 31 CAPACITOR HOLDER B01024 32 CAPACITOR 5 MF L01I001 33 MOTOR SUPPORT ASSEMBLY 1...

Page 62: ...PARTS LIST Model AMP LBM BMF 120 140 155 30 B50062A...

Page 63: ...TION AND BAFFLE 25 INSULATION LEFT SIDE PANEL B01800 02 26 HIGH LIMIT 175 20F R02R005 27 GASKET SMOKE BOX COVER B00205 28 GASKET FIXED BREECH BECKETT N04Z026 29A BURNER ASSEMBLY B03092 01 29B BURNER R...

Page 64: ...ine B02251 7B Urethane gasket 3 4 x 17 top B01526 80 24 Pump w ith solenoid valve N01Z068 7C Urethane gasket 3 4 x 22 1 2 bottom B01526 81 25 Wiring harness N01Z069 8 Pressure sw itch R99F022 26 Elect...

Reviews: