3. 

Communication 

3.1. 

RS-485 & CAN setting 

 

Default setting for RS-485: 

19200, n, 8, 1

 ,

for CAN:

 125K bps

 

 

DIP switch (SW1-SW6) is used for Modbus address(or 

CANopen Node ID) setting, default is 1, i.e. all OFF

 

For example:

 Modbus address(or CANopen Node ID) is 10

find the table of DIP switch 1-6 is 

ON, OFF, OFF, ON, OFF, OFF

 

 

SW1

SW6 setting 

Setting Modbus-RTU address for communication (1-64) 

Modbus Address 

SW 1 

  SW 2 

SW 3 

SW 4 

SW 5 

SW 6 

OFF 

OFF 

OFF 

OFF 

OFF 

OFF 

ON 

OFF 

OFF 

OFF 

OFF 

OFF 

OFF 

ON

 

OFF 

OFF 

OFF 

OFF 

ON

 

ON

 

OFF 

OFF 

OFF 

OFF 

OFF 

OFF 

ON

 

OFF 

OFF 

OFF 

ON

 

OFF 

ON

 

OFF 

OFF 

OFF 

OFF 

ON

 

ON

 

OFF 

OFF 

OFF 

ON

 

ON

 

ON

 

OFF 

OFF 

OFF 

OFF 

OFF 

OFF 

ON

 

OFF 

OFF 

10 

ON

 

OFF 

OFF 

ON

 

OFF 

OFF 

 

 

SW7

SW8 For Baud Rate Setting 

 

RS-485 

CAN 

  SW 7 

SW8 

9600 bps 

125k(Default) 

 

OFF 

OFF 

19200 (Default) 

 

250k bps 

ON 

OFF 

38400 bps 

500k bps 

OFF 

ON

 

115200 bps 

1M bps 

ON 

ON

 

 

PM-3133i

Select the different wiring mode   

(Please select the Software setting, if 1P2W-1CT or 1P3W-2CT is used) 

Models 

PM-3133i

 

PM-3133i-MTCP

 

Wiring 

SW 9 

SW 10 

SW 1 

SW 2 

Software setting 

OFF 

OFF 

OFF 

OFF 

3P3W-2CT 

ON

 

OFF 

ON

 

OFF 

3P3W-3CT 

OFF 

ON

 

OFF 

ON

 

3P4W-3CT 

ON

 

ON

 

ON

 

ON

 

 
 

3.2. Add the Bias Resistor on RS-485 Network for stable signal 

The RS-485 master is required to provide the bias for PM-31xx series. 

Otherwise, the tM-SG4 or SG-785 should be added to provide the bias. All 

ICP DAS controllers and converters provide the bias. 

 

Summary of Contents for PM-3133i

Page 1: ...r of electrical shock It is strongly recommended that all work should be performed only by qualified industrial electricians and metering specialist ICP DAS assumes no responsibility if your electrica...

Page 2: ...ility http ftp icpdas com pub cd powermeter pm 3133i 1 2 1 Limitation of Warranty This warranty does not apply to defects resulting from unauthorized modification misuse or use for reason other than e...

Page 3: ...hed CT s can be used The other CT s for example from panel will damage the instrument due to its large current around 5A or mA 3 When more than one smart meter PM 3133i series are installed please do...

Page 4: ...ing the terminal lines Otherwise it will cause severe injury 6 Please handle with extra care especially when the operation space of CT s is limited 7 The current direction must follow K L marked on CT...

Page 5: ...Start V1 00 Page 5 2 4 CT s installation steps At the bottom of the CT there is a K L mark Open the CT clip Make sure the power current direction follow the K L mark on the CT and then close the CT cl...

Page 6: ...ICP DAS Co LTD PM 3133i Quick Start V1 00 Page 6 2 5 Wiring 1P2W 1CT PM 3133i 1P3W 2CT PM 3133i...

Page 7: ...ICP DAS Co LTD PM 3133i Quick Start V1 00 Page 7 3P3W 3CT PM 3133i 3P4W 3CT PM 3133i...

Page 8: ...F ON OFF OFF OFF 7 OFF ON ON OFF OFF OFF 8 ON ON ON OFF OFF OFF 9 OFF OFF OFF ON OFF OFF 10 ON OFF OFF ON OFF OFF SW7 SW8 For Baud Rate Setting RS 485 CAN SW 7 SW8 9600 bps 125k Default OFF OFF 19200...

Reviews: