PET-AR400 User Manual
V1.0.0
P.55
Input Register (3xxxx) address table
Register Points
Description
Parameter
Data Type R/W Default
0
4
IEPE input
2’ comp HEX:
-10 ~ + 10 V
=-2147483648 ~
2147483647
Engineer Format:
-10 ~ + 10 V =
-10000000
~
+10000000
DWORD
R
-
80
1
Number of the DI channel
0
Word
R
-
81
1
Number of the DO channel
0
Word
R
-
82
1
Number of the AI channel
4
Word
R
-
83
1
Number of the AO channel
0
Word
R
-
84
1
Number of the Encoder channel 0
Word
R
-
90
1
OS image version
0 ~ 65535
Word
R
-
91
1
Firmware version
0 ~ 65535
Word
R
-
92
1
ET7H24 Library version
0 ~ 65535
Word
R
-
94
1
TCP library version
0 ~ 65535
Word
R
-
95
1
Web server library version
0 ~ 65535
Word
R
-
100
1
Read module name
0 x A400
Word
R
-
Holding Register (4xxxx) address table
Register Points
Description
Parameter
Data Type
R/W
Default
50
1
Read the boot count 1 ~ 65535
Word
R/W
-
51
1
Read module reboot
status
1
:
Power-on
2
:
Watchdog
3
:
Software reboot
Word
R
-
60
1
Modbus ID, always 1 0 ~ 255
Word
R
-