Appendix D: Modbus Application Notes
PET-7000 DIO User Manual, May 2009, V1.00, EMH-013-10----------
142
Appendix D: Modbus Application Notes
Dual Watchdog
Dual Watchdog consists of
Module Watchdog
and
Host Watchdog
.
The
Module Watchdog
is a built-in hardware circuit that will reset the CPU module if a failure
occurs in either the hardware or the software. If the application does not refresh the watchdog
timer within 0.8 seconds, the watchdog circuit will initiate a reset of the CPU.
The
Host Watchdog
is a software function that can be used to monitor the operating status
of the host. Its purpose is to prevent network communication problems or a host failure. If the
Watchdog timeout interval expires, the module will return all outputs to a predefined Safe
value (Refer to the
Safe Value
application note), which can prevent the controlled target from
unexpected situation.
AO address
40257
of the ET-7000 series Modbus register is the
address of the
Host Watchdog
timer, and will be stored into EEPROM. The WDT function
Summary of Contents for PET-7060
Page 1: ...PET 7000 series Power over Ethernet Remote I O Module User Manual For Digital I O Modules...
Page 41: ...Chapter 3 Web Configuration Page PET 7000 DIO User Manual May 2009 V1 00 EMH 013 10 41...
Page 51: ...Chapter 3 Web Configuration Page PET 7000 DIO User Manual May 2009 V1 00 EMH 013 10 51...
Page 52: ...Chapter 3 Web Configuration Page PET 7000 DIO User Manual May 2009 V1 00 EMH 013 10 52...
Page 72: ...Chapter 3 Web Configuration Page PET 7000 DIO User Manual May 2009 V1 00 EMH 013 10 72...