Section 4 I/O Module
Pulse Input
62
iDCS-8000 Hardware User Manual (2013/8/14, Rev: 1.43)
4.6
Pulse Input
4.6.1
F-8084
4.6.1.1
Overview
32-bit counter
8 up-counter/ frequency channels
1 ~ 32767 us digital filter
Falling/Rising/Both edge trigger
RoHS compliance
3000 VDC isolation from output to backplane
3000 VDC isolation from output to frame ground
Redundancy
No error counting when redundant switching
The F-8084 is a 32-bit high speed up-counter/frequency module. It can count up to 500 KHz input signal,
and accuracy of the frequency mode is +/-0.4% FSR. The F-8084 features many diagnostic like some
failures of communication, EEPROM, WDT, decoder, etc. When the modules are in the redundant mode
and a failure occurs the slave module will take over as soon as possible. Moreover, the redundant
switching is not only fast but also reliable for data exchanging. Thus, users can easily to use F-8084 to
count.
4.6.1.2
Specification
Parameter
Value
Feature
Redundant
Yes (The counting error less than 1
counter when input signal < 10 KHz)
Termination board break off detection
Yes
Digital filter
Yes (1~32767us)
LED indicator
1 RUN, 1 ACT, 1 DUX
Pulse Input
Number of channels
8
Type
Counter/Frequency
Min. Pulse Width
2 us
Input Frequency Range
1 Hz ~ 500 KHz
Rated Voltage
30 V
DC
Input voltage range, “1”
4.5 V
DC
~ 30 V
DC
Input voltage range, “0”
< 1 V
DC