I-7530, I-7530-FT, I-7530A, I-7565
User’s Manual (Version 1.3, Apr/2015) -------- 43
4.8 P1B [CHK]<CR>
Description:
Change the CAN configuration of CAN Converter
module. Module will be rebooted after saving these
parameters into EEPROM successfully.
Syntax: P1B[CHK]<CR>
P1
Command character
B
CAN Baud rate
Table: CAN baud rate list
B
Description
0
10K baud rate of CAN
1
20K baud rate of CAN
2
50K baud rate of CAN
3
100K baud rate of CAN
4
125K baud rate of CAN
5
250K baud rate of CAN, I-7530-FT does not support
6
500K baud rate of CAN, I-7530-FT does not support
7
800K baud rate of CAN, I-7530-FT does not support
8
1000K baud rate of CAN, I-7530-FT does not support
9
83.3K baud rate of CAN, I-7530-FT does not support
Response:
A valid command will write the CAN configuration baud
rate into the EEPROM and then reboot the module.
Invalid command: ?<Error Code><CR>
Note:
It is necessary to enable the “Error Response” function in the CAN
Converter Utility, in order to receive Syntax and/or communication
error information at the host PC. This command does not support
user-defined CAN baud rate function.
Example:
Command: P14<CR>
Set the CAN baud rate=125K into the I-7530 module and then
reboot the I-7530 module.