User’s Manual (Version 1.3, Apr/2015) -------- 17
2.5.1
Init/Normal DIP-Switch
The Init/Normal DIP-Switch is used to set the module run in the
configuration mode or the operation mode. After users get the module, the
configuration generally needs to be done first. Here is the description
about the Configuration mode and the Operation mode.
Configuration mode: This mode is used to set the UART or CAN
communication parameters for baud rate, data format, filter, etc. After
finishing the configuration, all of the parameters will be stored in the
EEPROM of the CAN converters.
Operation mode: This mode is used to convert the UART data and
CAN messages with each other. Users can also use the UART
commands to get module information or change some configuration of
the UART or CAN parameters. Some of UART commands like
“P2”
and
“P3” for changing the configuration in the normal mode will not be
stored in the EEPROM. About the detail description, please refer to
chapter 4 Command List.
The DIP-switch position for different modules may be different. The
DIP-switch of the I-7530/I-7530T, I-7530-FT, I-7530A, and I-7565 are on
the back of the module, as following figure.
The DIP-switch of the tM-7530 is in the bottom of the module.