I - 7 5 5 0 E Q u i c k S t a r t
( V e r s i o n 1 . 0 0 , J u n e / 2 0 1 4 )
P A G E
:
4
¾
Set the modules of the I-7550E
The user needs to set the number and size of the I/O modules in the
PROFIBUS configuration tool. The settings of the modules are described
below.
●
Max. I/O modules
:
32 modules
●
System setting module
:
20 Bytes output , 20 Bytes input
●
Output module
:
1~16 Bytes, 32Bytes, 64Bytes, 64 Words
●
Input module
:
1~16 Bytes, 32Bytes, 64Bytes, 64 Words
In any case, “System setting module” must be selected first. In this example,
we want to have 10 Bytes Input and 10 Byte Output, so we configure a
“System setting module”, a “10 Byte In” module and a “10 Byte Out” module
as below:
When the user finishes the configuration and saves setting in the PROFIBUS
Master station successfully, the 'RUN' LED indicator of I-7550E is turned on.
That shows the I-7550E working in the data exchange mode.
Configure module and click OK
button
Double click I-7550-E’s icon to
enter Slave configuration dialog
Step 4: Finish adding I-7550E in
the DP-master interface.
Step 3: Set address of I-7550E
and then click OK button.