I-7530A-MR Modbus RTU to CAN
Converter User’s Manual (Version 1.08, 07/2019) ------------- 52
4.7
P1B [CHK]<CR>
Description:
Change the CAN Baud rate configuration of the I-7530A-MR
module and then reboot the I-7530A-MR module.
Syntax: P1B[CHK]<CR>
P1
Command character
B
CAN Baud rate
Table 4-7: CAN baud rate list
B
Description
0
10 kbps baud rate of CAN
1
20 kbps baud rate of CAN
2
50 kbps baud rate of CAN
3
100 kbps baud rate of CAN
4
125 kbps baud rate of CAN
5
250 kbps baud rate of CAN
6
500 kbps baud rate of CAN
7
800 kbps baud rate of CAN
8
1000 kbps baud rate of CAN
9,A,B,C,D,E Reserved
F
User-defined baud rate of CAN
Response:
A valid command will write the CAN configuration baud rate
into the EEPROM and then reboot the I-7530A-MR module.
Invalid command: ?<Error Code><CR>
Note:
It is necessary to enable the
“Error Response” function while using
the UART2CAN Utility in order to receive Syntax and/or communication
error information.
Example:
Command: P14<CR>
Set the CAN baud rate=125 kbps into the I-7530A-MR module and
then reboot the I-7530A-MR module.