I-7530A-MR Modbus RTU to CAN
Converter User’s Manual (Version 1.08, 07/2019) ------------- 87
6.2.4 Using Modbus RTU command to configure module
I-7530A-MR supports five Modbus RTU commands (function code 10
hex
) of
configuring module, including reboot module, reset CAN bus, change RS-
232/RS-422/RS-485 setting, change CAN bus baud rate, and change CAN bus
user-defined baud rate. These commands use start address 0100
hex
.
Example: Using Modbus RTU command to reboot module.
Figure 6-8: Using Modbus RTU command to reboot module