I-7530A-MR Modbus RTU to CAN
Converter User’s Manual (Version 1.08, 07/2019) ------------- 90
7. Modbus Master Mode
To compare with the chapter 5, this section will introduce the Modbus
master mode of the I-7530A-MR. Via this function, the I-7530A-MR can act as a
Modbus master to CAN module. Following, this sector will illustrate how to
configure and how to operate the function in detail.
Note: This function is supported by firmware version v2.00 or later.
7.1
Supported Modbus Functions
The Modbus Master function supports Modbus function code: 0x01, 0x02,
0x03, 0x04, 0x05, 0x06, 0x0F, and 0x10. The following table will describe in
detail.
Table 6-1: Supported Modbus Function Codes
Modbus
command
Function
Code
Function Name
Description
Modbus
Read
command
1 (01 Hex)
Read Coil Status
Read Coil Status from slave
device.
2 (02 Hex)
Read Input Status
Read Input Status from slave
device.
3 (03 Hex)
Read AO Holding
Registers
Read AO Holding Registers
from slave device.
4 (04 Hex)
Read AI Registers
Read AI Registers from slave
device.
Modbus
Write
command
5 (05 Hex)
Write Single Coil
Write Single Coil from slave
device.
6 (06 Hex)
Write Signal
Register
Write Single Register from
slave device.
15 (0F Hex)
Write Multiple Coil
Write Multiple Coil from slave
device.
16 (10 Hex)
Write Multiple
Registers
Write Multiple Registers from
slave device.