HRT-710 User Manual (Version 1.24, June/2015) PAGE: 52
will re-send the HART Cmd for
―Retry count‖ times.
(5) The following are the Com Port comm. setting of HRT-710.
[1] Baud Rate
:
1200~115200 bps.
[2] Data Bits
:
7 or 8.
[3] Stop Bits
:
1 or 2
[4] Parity
:
None / Odd / Even.
[5] Net ID
:
1~247.
[6] Protocol
:
MB RTU Slave or MB ASCII Slave.
[7] Swap mode
:
None / Byte / Word / W&B (The swap mode of
Modbus comm.)
EX
:
2 words data (0x1234, 0x5678) from HRT-710. Users can set
the swap mode for different data format.
Swap mode
Data
None
0x1234 0x5678
Byte
0x3412 0x7856
Word
0x5678 0x1234
W&B
0x7856 0x3412
2.
―Module Edit‖ window:
Figure 41
:
The
―Module Edit‖ window
It is used to set the comm. mode for HART devices.
(1) Channel
:
0~7. (Only channel 0 supports now)
(2) Auto Configure
:
If enables this function, HRT-710 will detect the
―frame type‖, ―address‖, ―preambles‖, ―manufacturer ID‖, ―device
type
‖ and ―device ID‖ of HART device automatically.