GW-7552-B / GW-7552-M PROFIBUS/MODBUS GATEWAY User Manual
(Version 1.60, May/2017)
PAGE: 50
then set the value of the first byte from 0 to 1 to trigger the data output
command.
--Send Command to read DI of the GW-7552-B again
Now the user can input command (“01 02 00 00 00 10”) in MBRTU and click
<Send Command> button to send Modbus command: “01 02 00 00 00 10 79
C6” again. Then MBRTU can receive response message (“01 02 02 FE DC
F8 41”). In this message, the user can know the value of DI0 & DI1 have
changed to “0xFE” & “0xDC” in the GW-7552-B, as shown in
figure 47, 48,
49
&
table 16.
Figure 47 Send Modbus command to read DI of the GW-7552-B