GW-7552-B / GW-7552-M PROFIBUS/MODBUS GATEWAY User Manual
(Version 1.60, May/2017)
PAGE: 36
7552-B / GW-7552-M is slave.
4.4 The Configuration of the modules
The user can set the number and size of the I/O modules in the PROFIBUS
configuration tool. The settings of the modules are described below.
●
Max. I/O modules
:
32 modules
●
System setting module
:
3 byte out , 4 byte input
●
Output module
:
Output Relay/Coil => 1~32 Bytes
Output Register => 1~64 Words
●
Input module
:
Input Relay/Coil => 1~32 Bytes
Input Register => 1~64 Words
●
Max. length of I/O data
:
263 Bytes
●
Output length
:
0~131 Bytes
●
Input length
:
0~132 Bytes
The modules have module parameters about the communication settings. The
module parameters are shown in the below
:
A. Output Relay/Coil module parameters
:
●
Modbus Slave Device ID(M)
:
0~247
●
Start Address(M)
:
0~65535
●
NO. of Relay/Coil(M)
:
8*(n-1)+1 ~ 8*n Bits
n=Module size/Byte
B. Output Register module parameters
:
●
Modbus Slave Device ID (M)
:
0~247
●
Start Address(M)
:
0~65535
●
Change Word Order
:
Enable/Disable (Even module only)
C. Input Relay/Coil module parameters
:
●
Modbus Slave Device ID (M)
:
0~247
●
Start Address(M)
:
0~65535
●
NO. of Relay/Coil(M)
:
8*(n-1)+1 ~ 8*n Bits
●
Module Type(M)
:
Read DI/DO
n=Module size/Byte
D. Input Register module parameters
:
●
Modbus Slave Device ID (M)
:
0~247
●
Start Address(M)
:
0~65535
●
Module Type(M)
:
Read AI/AO