ET-87P2/4/8 Series User Manual, version 1.0.1 Page: 89
Copyright © 2011 ICP DAS Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com
Error
Code
Slot
LED
(Red)
Status
Description
Solution
operation.
04H
Bright
(Error)
wrong
Configuration
format
Configure failure:
1. Run DCON Utility.
2. Click the "Write To 87Pn"
button to write the settings
to 87Pn CPU again.
The format of
configured
commands is wrong
for DCON Protocol.
05H
Bright
(Error)
Read
Configuration
failed
The memory data is
failed
:
1. Run DCON Utility.
2. Click the "Write To 87Pn"
button to write the settings
to 87Pn CPU again.
The configured
commands are
wrong for DCON
Protocol.
06H
Bright
(Error)
Cannot find
module
The configured
module at this slot
has been removed. It
is empty now.
1. Please insert a correct
module as previous
configured one.
2. Or configure with DCON
Utility as "Empty" and click
the "Write To 87Pn" button
to write the configuration to
87Pn CPU.
07H
Bright
(Error)
Incorrect
module name
Configure failure:
The insert & configure
module name are different,
insert the correct one or run
the Dcon Utility to modify
the settings accord with the
module name.
The module inserted
in this slot is not the
same as previous
configured.
08H
Bright
(Error)
Internal INIT*
pin failed
Configure failure:
1. Please restart the power
to initialize to I/O module
2. If it still failed to initialize,
send it back to factory to
check.
Note: RU-87Pn only
supports high profile 87K
I/O modules.
The INIT Pin is failed
to connect with the
GND and module
failed to initialize.