background image

Technical support: 

[email protected]

                                                    P5 

4  

Modbus Address 

 

(0xxxx) DO address:

 

Begin 

address 

Points 

Description 

Bits 

Per 

Point 

Range 

Access 

Type 

0 (0x0) 

1~6 

Digital Output Channels 

0: OFF, 1: ON 

R/W 

32 (0x20) 

Clears the status of all high 

latched DI channels 

1: Clear 

33 (0x21) 

Clears the status of all low 

latched DI channels 

1: Clear 

190 

(0xBE) 

1~6 

Enables frequency 

measurement for all DI 

Channels 

0: Disable 

1: Enable 

(Default: 0) 

R/W/F 

235 

(0xEB) 

1~6 

Sets the Power-on value for 

all DO Channels 

0: OFF, 1: ON 

(Default: 0) 

R/W/F 

267 

(0x10B) 

1~6 

Sets the Safe value for all DO 

Channels 

0: OFF, 1: ON 

(Default: 0) 

R/W/F 

“R”

: Read; 

“W”

: Write;

 

“F”

:

 

Settings are recorded in flash memory by default 

 

 

(1xxxx) DI address:

 

Begin 

address 

Points 

Description 

Bits 

Per 

Point 

Range 

Access 

Type 

(0x0) 

1~6 

Digital Input 

0:Off 
1:On 

32 

(0x20) 

1~6 

Digital latched status (high) 

0:no 

1:latched 

64 

(0x40) 

1~6 

Digital latched status (low) 

0:no 

1:latched 

“R”

: Read

 

 

Note 

For detail “DI/DO Modbus Address” information, refer to Section 6.3 Modbus Register Table

 

of user’s manual (

http://ftp.icpdas.com/pub/cd/6000cd/napdos/et2200/document/

).

 

 

 
 

 

Summary of Contents for ET-2260

Page 1: ...60 Quick Start v1 2 Jun 2018 What s in the box Related Information The package includes the following items ET 2260 Module x 1 Quick Start x1 This Document ET 2200 Series Product Page Documentation Fi...

Page 2: ...your Windows firewall and Anti Virus firewall first else the Search Servers on Chapter 5 may not work Please contact with your system Administrator 2 Connect both the ET 2260 and your PC to the same...

Page 3: ...N or 4 VDC Digital Input Counter Sink Source To other channels 10K DICOM DIx To other channels 10K DICOM DIx To other channels 10K DICOM DIx To other channels 10K DICOM DIx Relay Close Open Close to G...

Page 4: ...the DI and DO for Self test A tip for connecting the wire to the connector A tip for removing the wire from the connector 1 Connect the NO0 pin Pin01 to the GND pin Pin02 2 Connect the COM0 pin Pin03...

Page 5: ...EB 1 6 Sets the Power on value for all DO Channels 1 0 OFF 1 ON Default 0 R W F 267 0x10B 1 6 Sets the Safe value for all DO Channels 1 0 OFF 1 ON Default 0 R W F R Read W Write F Settings are recorde...

Page 6: ...Search Servers to search your ET 2260 3 Double click your ET 2260 to configure the settings Factory Default Settings of ET 2260 IP Address 192 168 255 1 Subnet Mask 255 255 0 0 Gateway 192 168 0 1 4...

Page 7: ...the ET 2260 is working well with new configuration 2 Click the name of ET 2260 to select it 3 Click the Web button to log in to the web configuration pages Or enter the URL address of the ET 2260 in t...

Page 8: ...as com P8 5 In the Home page allows a simple test to be performed to verify the Digital Input and Output functionality 6 In the Digital I O section click the DO0 button to ON Red 7 The corresponding D...

Reviews: