DL-100S-E / DL-101S-E / DL-110-E / DL-120-E User Manual Version 1.0.0 May 2020
- 67 -
Address Description
Attribute
40564
TCP disconnection timeout value, 5 to 65535, in
second, 0 to disable.
Only for Modbus TCP protocol
R/W
40565
Module reset timeout value, 30 to 65535, in
second, 0 to disable.
Only for Modbus TCP protocol
R/W
40865
RTC year, 2000 to 2159
R/W
40866
RTC month, 1 to 12
R/W
40867
RTC date, 1 to 31
R/W
40868
RTC hour, 0 to 23
R/W
40869
RTC minute, 0 to 59
R/W
40870
RTC second, 0 to 59
R/W
40871
Total number of log records, low word
R
40872
Total number of log records, high word
R
40873
The starting record to read log data, low word
R/W
40874
The starting record to read log data, high word
R/W
40875
The status of the data logging, 0: stopped, 1:
running
R
40876
The data logger command, 0: stop, 1: run, 2: run
in period mode
R/W
40877
Continue writing when data logger is full, 0: no, 1:
yes
R/W
40878
Hour of the data logger sampling period, 0 ~ 24
R/W
40879
Minute of the data logger sampling period, 0 ~ 59 R/W
40880
Second of the data logger sampling period, 0 ~ 59 R/W
40881
Starting year when logging in period mode, 2000
~ 2159
R/W
40882
Starting month when logging in period mode, 1 ~
12
R/W
40883
Starting date when logging in period mode, 1 ~ 31 R/W
40884
Starting hour when logging in period mode, 0 ~ 23 R/W
40885
Starting minute when logging in period mode, 0 ~
59
R/W