7.2.6 Reset Service
This service can reset the device. If users want to reset the device, they can
apply this service to the device
The parameter type for the reset common service has the following bit
specifications:
Value
Type of Reset
0
Emulate as closely as possible cycling power on the item the
Identity object represents.
1
Return as closely as possible to the out-of-box configuration,
then emulate the cycling power as closely as possible.
Note: CAN-8x24: Node ID=0x09, Master node ID=0x0A
1. Requests the use of the Predefined Master/Slave Connection set
Master
(MAC
ID
=0x0A)
Slave
(MAC
ID
=0x09)
_ Group 2 Message
| _ Destination MAC ID=0x09
| | _ Message ID =6
| | | _ Frag=0. Transaction ID=0. Souce MAC ID= 0x0A
| | | | _ Service=Allocate_Master/Slave_Connection_Set Request
| | | | | _ Class ID=3
| | | | | | _ Instance ID=1
| | | | | | | _ Allocation Choice= Explicit
| | | | | | | | _ Allocator’s MAC ID=0x0A
ID=10 001001 110. Data= 0A 4B 03 01 01 0A
_ Group 2 Message
| _ Source MAC ID=0x09
| | _ Message ID =3
| | | _ Frag=0. Transaction ID=0. Souce MAC ID= 0x0A
| | | | _ Service=Allocate_Master/Slave_Connection_Set Response
| | | | | _Connection Message Body Format = DeviceNet (8/8)
| | | | | |
| | | | | |
| | | | | |
ID=10 001001 011. Data= 0A CB 00