5.2.27 Sub-FC70(0x46): Get 8 Locked Periods
This command gets 8 locked periods in a day from module. One locked period composed
of Start Time and End Time. The End Time should be late after the Start Time.
Table 5-57: FC100-Sub-FC70 Request
Byte
order
Description
Size
Value
00
Address
1 Byte
1 ~ 247 (Net ID)
01
FC
1 Byte
0x64
02
Sub-FC
1 Byte
0x46
Table 5-58: FC100-Sub-FC70 Response
Byte
order
Description
Size
Value
00
Address
1 Byte
1 ~ 247 (Net ID)
01
FC
1 Byte
0x64
02
Sub-FC
1 Byte
0x46
03
P1 Start Hour
1 Byte
0 ~ 23, period 1 start Hour
04
P1 Start Minute
1 Byte
0 ~ 59, period 1 start Minute
05
P1 Start Second
1 Byte
0 ~ 59, period 1 start second
06
P1 End Hour
1 Byte
0 ~ 23, period 1 end Hour
07
P1 End Minute
1 Byte
0 ~ 59, period 1 end Minute
08
P1 End Second
1 Byte
0 ~ 59, period 1 end second
09~44 P
2 to P7 …
36 Bytes
period 2 ~ 7 start time and end time
45
P8 Start Hour
1 Byte
0x00
46
P8 Start Minute
1 Byte
0x00 ~ 0xFF, enabled state of 8 periods
47
P8 Start Second
1 Byte
0x00
48
P8 End Hour
1 Byte
0x00 ~ 0xFF, enabled state of 8 periods
49
P8 End Minute
1 Byte
0x00
50
P8 End Second
1 Byte
0x00 ~ 0xFF, enabled state of 8 periods