![background image](http://html.mh-extra.com/html/icp-das-usa/acs-20b-mrtu/acs-20b-mrtu_user-manual_614668044.webp)
ACS-20B(W)-MRTU User Manual
Version 1.1
Page
:
44
Copyright © 2021 ICP DAS Co., Ltd. All Rights Reserved E-mail: [email protected]
5.2.18 Sub-FC45(0x2D): Set Inverted Red/Blue LED Status
Table 5-39: FC100-Sub-FC45 Request
Byte
order
Description
Size
Value
00
Address
1 Byte
1 ~ 247 (Net ID)
01
FC
1 Byte
0x64
02
Sub-FC
1 Byte
0x2D
03
Inverted
Red/Blue LED
State
1 Byte
0 => default Red(Standby) / Blue(Sensing);
1 => Red(Sensing) / Blue(Standby)
Table 5-40: FC100-Sub-FC45 Response
Byte
order
Description
Size
Value
00
Address
1 Byte
1 ~ 247 (Net ID)
01
FC
1 Byte
0x64
02
Sub-FC
1 Byte
0x2D
03
Result
1 Byte
0x00 => OK
0xFF => Error