ACS-20B(W)-MRTU User Manual
Version 1.1
Page
:
30
Copyright © 2021 ICP DAS Co., Ltd. All Rights Reserved E-mail: [email protected]
5.2.4 Sub-FC06 (0x06): Set Communication Settings
Table 5-11: FC100-Sub-FC06 Request
Byte
order
Description
Size
Value
00
Address
1 Byte
1 ~ 247 (Net ID)
01
FC
1 Byte
0x64
02
Sub-FC
1 Byte
0x05
03
New NetID
1 Byte
1 ~ 247 (Net ID) of the module
04
Baud rate
1 Byte
6 ~ 10 (baud rate index)
=> {9600, 19200, 38400, 57600, 115200} bps
05
Parity
1 Byte
0, 1, 2=>{None, Odd, Even} (default: None)
06
Reserved
1 Byte
0x00
07
Stop bits
1 Byte
1, 2 (default: 1)
08
Modbus
response
delay
1 Byte
0 ~ 30 ms (default: 1 ms)
09
Change
Setting
1 Byte
0=>The settings are effective after power
cycling.
1=>Change settings immediately
Table 5-12: FC100-Sub-FC06 Response
Byte
order
Description
Size
Value
00
Address
1 Byte
1 ~ 247 (Net ID)
01
FC
1 Byte
0x64
02
Sub-FC
1 Byte
0x05
03
Result
1 Byte
0=>OK
0xFF=>Error