ACS-20B(W)-MRTU User Manual
Version 1.1
Page
:
29
Copyright © 2021 ICP DAS Co., Ltd. All Rights Reserved E-mail: [email protected]
5.2.3 Sub-FC05 (0x05): Get Communication Settings
Table 5-9: FC100-Sub-FC05 Request
Byte
order
Description
Size
Value
00
Address
1 Byte
1 ~ 247 (Net ID)
01
FC
1 Byte
0x64
02
Sub-FC
1 Byte
0x05
03
reserved
1 Byte
0x00
Table 5-10: FC100-Sub-FC05 Response
Byte
order
Description
Size
Value
00
Address
1 Byte
1 ~ 247 (Net ID)
01
FC
1 Byte
0x64
02
Sub-FC
1 Byte
0x05
03
Net ID
1 Byte
1 ~ 247 (Net ID) of the module
04
Baud rate
1 Byte
6 ~ 10 (baud rate index)
=> {9600, 19200, 38400, 57600, 115200} bps
05
Parity
1 Byte
0, 1, 2=>{None, Odd, Even} (default: None)
06
Data bits
1 Byte
8 (fixed)
07
Stop bits
1 Byte
1, 2 (default: 1)
08
Modbus
response
delay
1 Byte
0 ~ 30 ms (default: 1 ms)
09
Reserved
1 Byte
0x00