iCool Turbo Dual Temp Installation & Operation Manual Download Page 4

Page 4

Advice About Water And Pools. 

If you are using your TurboCool with an iCool brand spa pool , the pool is provided with a high quality spa water 
pump especially designed for the purpose. The pumps we provide are resistant to chlorine and salt water at normal 
concentrations, but the use of chemicals should be kept within the range normally recommended for swimming pools 
to prolong the life of the pump and the titanium heat exchanger tanks inside the unit. 

If You Are Providing Your Own Spa Pool

 

we recommended that you use a

 pump of no more than 450 

watts

 to circulate pool water to and from the iCool. High pressure spa jet pumps of more than 500 watts should not 

be connected to the iCool because the very high pressure from such pumps could damage the water seals. 

If high pressure water jets are required

 

they must be connected to a separate water circuit and a separate 

pump that is specifically for the massage jets. Do not connect High pressure pool pumps or spa jet pumps to the 

TurboCool circulation system as it would damage the titanium heat exchangers and also the flow rate would be much 

too fast for efficient cooling. The TurboCool must have it’s own independent pump and plumbing. High pressure jets 

are not normally used in ice baths because they heat the water by injecting and circulating room air.

Avoid Harsh Chemicals. 

Never use bromide

 as it is highly corrosive to all materials and can cause irritation 

to athletes eyes and skin. Bromide is unnecessary in cold pools because bacterial growth is much slower at low 
temperatures. A small amount of chlorine is all that is needed to keep the water safe. Use standard pool test strips 
to determine the amount needed. If the water is emptied after each session then no chemicals are needed.

The Pump Should Never Be Run Without Proper Water Flow. 

The main components of most pool 

pumps are lubricated by the water flow, therefore major damage can occur if the pump is run without water. To 

protect the pump, your iCool has an automatic water flow monitoring system that will shut the system down and stop 

the pump if no water flows for more than 2 minutes.

Priming The System With Water.

The pump must be primed with water before it can provide proper circulation. If your spa pool is level with or above 

the pump then there is generally no need to prime the system as the water will flow by gravity to the pump. If water 

does not flow after more than 2 minutes the iCool will shut down to protect the pump against over heating. 

If your pump has a lint basket

 please ensure that it clean and that it is full of water before starting the pump. 

If the water does not begin to flow after about 30 seconds, stop the pump and open the lint basket , fill it with water 

again, close the lid and start the pump again. This will normally provide enough suction to get the system primed 
and circulating correctly.

iCool Spas With Built In Filtration Systems (optional extra).

 

Some iCool spas and pools have built 

in cartridge filtration systems. Before starting the water circulating pump, check that the filter is clean and that the 

filter housing is full of water. Open the air valve on the filter housing to allow trapped air to be released and close it 

as soon as a steady flow of water is observed.

Keep Filters And Link Baskets Clean.

 

The lint basket on pool pumps (if provided) traps any larger objects 

that may get sucked back from the pool and it should be emptied whenever necessary. Your pools’ filter cartridge 

should be removed and cleaned whenever the pressure shown on the gauge on the top of the filter indicates that 

the filter is becoming clogged. If there is no gauge on your model, unscrew the lid of the filter housing and look to 

see if the filter is clean or clogged with dirt. If the filter is not cleaned then eventually the TurboCool will shut down 

due to low water flow.

Check For Air Leaks

.

Water should begin circulating within 2 minutes after the system pump is started. If it does not, the system will stop 
the pump. 

If water does not circulate after 2 or 3 attempted starts, then there may be an air leak

 in either the pipes 

from the spa or the pipe fittings or a blockage in a pipe or filter. This must be corrected. 

Limits to the Electric Shock Protection System 

The iCool residual earth leakage protec-

tion system can only protect against devices actually connected to the iCool. It can not protect against faults 
in other unrelated electric devices in the area. All electric devices in any pool area must only be connected to 
a power supply that has a residual earth leakage device either at the main switch board or on the device itself. 

Never risk using unprotected electrical devices near water.

Summary of Contents for Turbo Dual Temp

Page 1: ...Installation Operation Manual Turbo Cool Turbo Dual Temp 2012 Models ...

Page 2: ...Connections Page 9 Installing the Pump Page 9 Operating your TurboCool in Cold Mode Pages 10 to 12 Operating your TurboCool in Heat Mode Page 12 Detailed Function Description Page 13 Setting System Preferences Page 14 Timers and Clock Pages 15 to 16 Locking the Touch Screen Page 16 Digital Power Management Page 16 Trouble Shooting Page 17 Specifications Page 18 Contents ...

Page 3: ...ularly The main power switch is also part of the electrical safety circuit that can prevent the possibility of electric shock It is essential to test this safety system each time you use the iCool to make certain it is operating correctly This takes only a few seconds To Test the Earth Leakage Safety Device Turn on the main switch and then press the test button on the switch body If the safety sys...

Page 4: ... your spa pool is level with or above the pump then there is generally no need to prime the system as the water will flow by gravity to the pump If water does not flow after more than 2 minutes the iCool will shut down to protect the pump against over heating If your pump has a lint basket please ensure that it clean and that it is full of water before starting the pump If the water does not begin...

Page 5: ...gher and restart Normally settings above 8ºC or or 45ºF will not freeze the tanks in any conditions Safe Temperature Settings Following international safety reccomendations your iCool will not accept water temperature settings below 5ºC or 40ºF as this would put athletes using the system at risk of hypothermia The tanks can only freeze if your setting is below 7 to 8ºC and this can only happen in ...

Page 6: ...special connection to 3 phase power whereas the TurboCool only requires single phase power This is new technology developed by iCool and has many advantages The Intelligent Control System Saves a Lot of Electricity Firstly start up current is much lower because the built in digital control makes sure that the 2 systems never start at exactly the same time so it never exceeds the rating of a normal...

Page 7: ...be at least 500 mm apart This spacing can be reduced if they are installed front to back as shown in the illustration at bottom right Plumbing Requirements Just 2 standard 40mm PVC pool water pipes are required for each TurboCool Spa installation for carrying water to and from the spa The TurboCool can be up to a maximum of 25 meters from the Spa Pool and it can be up to 5 meters above or below th...

Page 8: ...cables that you must unplug in order to mount the back panel to a wall STEP 3 Unplug the 3 cables as shown so that the front can be separated from the rear panel STEP 4 The rear panel has several holes that can be used for screwing to a wall Select a good position where the screen can be easily reached by operators and can be seen from the recovery spa STEP 5 Replace the 3 plugs as shown Push the ...

Page 9: ...ect your TurboCool is to a wall box with an isolation switch however because the iCool also has an isolation safety switch and an earth leakage safety device built in you can also simply attach a power plug and plug that into a standard wall socket Connecting the Pump Depending on your order on the rear of your TurboCool there will either be a standard AC power socket or a splash proof connection ...

Page 10: ...take about 20 seconds and the screen will be black for about 10 seconds Touch the WELCOME screen anywhere and the Main Operating Screen will appear The status bar will flash white while the software loads and the system is checked The STATUS LIGHTS bar above the touch screen will change colour or flash to give a clear indication of each function While the software is loading the system conducts an...

Page 11: ...ature Selection Screen and accepted 15ºC then you will still be seeing the Main Operating Screen NOTE The temperatures can also be displayed in Fahrenheit This is explained on page 14 of this Manual STEP 3 Start the Water Pump Touch the Start Pump button The pump will begin operating and water should begin circulating within a minute or so Please note When you touch the main buttons they change fr...

Page 12: ...AT Do not operate the HEAT COLD switch while the iCool is running Turn off the main power first then change the switch position and turn the main power back on In HEAT mode the fans will immediately lock on to medium speed which is the most efficient setting for heating A green light on the bottom right hand of the Turbo cabinet will light to indicate that heating mode reverse cycle is selected In...

Page 13: ...hing the Change Setting button this will take you to the Change Settings Screen From here you proceed as described on page 11 Lights Some iCool models have convenient area lighting which is very helpful if the area around your installation is not well lit Touching the Lights button takes you to a simple screen that has both ON and OFF light buttons When you touch the ON button the area lights illu...

Page 14: ...reference To return to the main operating screen touch the BACK 1 button 14 10 25 Systems Preferences Available System Preferences Touching the Home button will take you to a screen that will give you access to the SYSTEMS SETTINGS that allow you to customise certain settings to your preference Optimum settings are automatically selected so there is normally no need to use this feature Main Coolin...

Page 15: ...n screen illustrated below This screen allows you to see the countdown from a distance and also to control it in various convenient ways The current pool and outside temperature will also be displayed The count down can be set for once only or it can repeat automatically as many times as you like This is particularly convenient if you have a number of athletes using the same pool at the same time ...

Page 16: ...horised operators iCool Systems have attractive user interfaces this makes them easy to use but the downside is that untrained people often like to play with the colourful touchscreens This can upset all your settings and even cause an unintended shutdown To lock the screen so that no further inputs can be made touch and hold the iCool icon on the main run screen for more than 10 seconds you can o...

Page 17: ...explanation and advice on how to correct this If the iCool shuts down and displays a System Too Hot Red Warning Screen Your TurboCool is very powerful and can remove as much as 10 000 watts of heat per hour from your pool Naturally this heat has to be removed into the air surrounding the system The powerful internal fans can normally handle this with ease however if the air flow around the iCool i...

Page 18: ...er Management System Digital 4 parameter Digital 4 parameter Standard Mounting Available Mounting Options Anti Vibration Feet Wall Frame Ceiling Frame Roller Wheels Anti Vibration Feet Wall Frame Ceiling Frame Roller Wheels Area Lighting Built In 10 Watts 10 Watts Standard User Control and Information System Colour Touch Screen High Resolution LCD Colour Touch Screen High Resolution LCD Electrical...

Reviews: