3.4.6 Horizontal Wall Vent Termination type C
11
Flue sizing:
Iconic 1100 : Ø130/200 Connector on Appliance.
Ø130/200 Maybe used Throughout, Alternatively,
Ø100/150, Reducer may be used, so that Ø100/150 flue
can be used thereafter.
Recommended pipes by
HOLETHERM (Other flue brands CE approves, are On-Top, Poujoulat and M&G).
Maximum pipe extension, for outside wall (H)
= 2 X Vertical Pipe Rise (V) =1 x (H) Horisontal For
Ø130/200 flue.
= 1 X Vertical Pipe Rise (V) =1 x (H) Horisontal For
Ø100/150 flue.
Maximum Permissible run (H) =13 (Including bends, every 90o Bend is 0.5m' flue).
Vertical Flue Rise
(V) metres
Max. Horizontal Flue Run, (H) m
for Ø130/200 flue
Max. Horizontal Flue Run, (H) m
for Ø100/150 flue
0.5
1
0.5
1
2.5
1
1.5
3.5
1.5
2
4
2
2.5
4.5
2.5
3
5
3
3.5
5
3.5
4
7
4
4.5
7
4.5
5
8
5
Minimum Vertical Flue Height for Iconic 1100 - 0.5m
Summary of Contents for 1100 Front
Page 3: ...3 Iconic 1100 Bay ICONIC1100 3S ...
Page 4: ...IE GB 4 Iconic 1100 Corner Left Right IC1100 CL CR ...
Page 5: ...5 Iconic 1100 Room Divider ICONIC1100 RD ...
Page 6: ...IE GB 6 Iconic 1100 See Through IC1100 ST ...
Page 19: ...19 3 3 3 Mantel Clearances 3 3 3 a Combustible Mantel Side view ...
Page 20: ...IE GB 20 ...
Page 21: ...21 3 3 3 b Combustible Mantel Side Wall Top view ...
Page 25: ...25 Horizontal Wall Vent Termination Category 1 for 200 130 type C11 ...
Page 27: ...27 Typical Installations ...
Page 32: ...IE GB 32 ...
Page 34: ...IE GB 34 3 5 5 Iconic 1100 Pebble Effect ...
Page 43: ...43 Annex 1 ...
Page 44: ...IE GB 44 ...
Page 45: ...45 ...
Page 46: ...IE GB 46 ...
Page 47: ...47 ...